Electrical Application Details for App #: Y147863
Premises: 745 HUNTS POINT AVENUE BRONX BIN: 2006530     Block: 2763   Lot: 149
   
Application Completed and Certified

Filed: 744 COSTER ST Census Tract:   99 Health Area:  4300
BASEMENT Admin Area:   Y - BRONX Inspection Area:   J
BRONX, NY 10474 Community Board:   202
Special Place Name:   134 AVE
DOB Cross Street(s):   SPOFFORD AVENUE,    HUNTS POINT AVENUE
Status:   C - JOB IS SIGNED OFF 02/09/2011
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  08/06/2009 11:48 AM
Application Entered:   08/06/2009 Job Start Date:   08/07/2009
Last Change:   02/09/2011 Job End Date:   09/23/2009
Appointment Status:   
Last Inspection By:   ASHMAN, K.       On     11/03/2010      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011673 Licensee Name: DONALD P WHITE
Firm: 003956 Firm Name: DNR ELECTRIC INCORPORATE
Firm Phone: 347-293-4726  Firm Address: 2323 HAVILAND AVENUE BRONX NY 10462 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
9 - OTHER
Total Fee:  $250.00
Other Work:   METER UPGRADE
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: MURICE MCKENZIE
Owner Business Name: 744 COSTER BRONX LLC
Authorized Representative:  PARVAWATTIE RAGHUNANDAN
Relationship To Owner:   SUPER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  ONE 400 DISSCONECT
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  1  3# 3/0 THHN
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  1  ONE SET OF 500 MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 05/10/2010 Notice: C - CALL TO OFFICE 05/10/2010
Power Issued: 05/10/2010 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Y147863
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 04/20/2010 04/27/2010 GYM A (95) (7) Y
INSPECTION COMMENTS: VIOL
 
(2) 05/05/2010 05/10/2010 GYM H X E (50) (0) Y
INSPECTION COMMENTS: C
 
(3) 11/03/2010 11/17/2010 KAS C R E (25) (0) Y
INSPECTION COMMENTS: C

OBJECTION FOR APPLICATION #: Y147863
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
BSMT/ART 250.53D NO SUPPLEMENTAL ELECTRODE IS PROVIDED
RSLV 04/20/2010 05/05/2010 11/03/2010
 
002 (999) OTHER
A)BSMT/ART 250.24 ALL SVC SWS NEUTRAL MUST BE BONDED
RSLV 04/20/2010 05/05/2010 11/03/2010
 
003 (999) OTHER
B)BSMT GROUNDING FROM 4000A SER.SW TO WATER MAIN IS NOT AS PER TABLE250.66
RSLV 04/20/2010 05/05/2010 11/03/2010
 
004 ( 7) EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT)
BSMT/EMT TUBING TO METER BANKS
RSLV 04/20/2010 05/05/2010 11/03/2010
 
005 ( 29) OUTLET BOXES ARE NOT COVERED
BSMT/1900 BOX GROUDING ELECTRODE RACEWAY TO WATERMAIN
RSLV 04/20/2010 05/05/2010 11/03/2010
 
006 ( 25) ARMORED CABLES ARE NOT PROPERLY TERMINATED
BSMT/NEUTRAL 3/0 WIRE METER BANKS
RSLV 04/20/2010 05/05/2010 11/03/2010
 
007 (999) OTHER
C)BSMT/ART 250.68 GROUNDING ELECTRODE CONDUCTOR IS NOT ACCESSBILE ATWATER MAIN
RSLV 04/20/2010 05/05/2010 11/03/2010



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.