| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
1 |
400A |
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
1 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
1 |
500MCM |
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
1 |
24 CKT |
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(999) |
OTHER (A) NEC ARTICLE NYC AMENDMENT 230.4913 THREADLESS FITTING USED ON OVERHEAD SERVICE CONDUIT |
OPEN |
12/21/2009 |
12/21/2009 |
|
| |
| 002 |
(999) |
OTHER (B) NEC ARTICLE 250.28 NUETRAL NOT BONDED IN 400AMP SERVICE SWICTH |
OPEN |
12/21/2009 |
12/21/2009 |
|
| |
| 003 |
(999) |
OTHER (C) NEC ARTICLE 250.68 WATERMAIN GROUNDING ELECTRODE NOTPROVIDED FOR 400 AMP SERVICE SWITCH |
OPEN |
12/21/2009 |
12/21/2009 |
|
| |
| 004 |
(999) |
OTHER (D) NEC ARTICLE 250.53.D.1 EATER METER BONDING JUMPOER NOT PROVIDED |
OPEN |
12/21/2009 |
12/21/2009 |
|
| |
| 005 |
(999) |
OTHER (E) NEC ARTICLE 230.4 LINE AND LOAD IN SAME ENCLOSEURE PL & P METERTAP |
OPEN |
12/21/2009 |
12/21/2009 |
|
| |
| 006 |
(999) |
OTHER (F) NEC ARTICLE 310.16 #12 EXISTING APT RISERS FUSED AT 60 AMP |
OPEN |
12/21/2009 |
12/21/2009 |
|
| |
| 007 |
(999) |
OTHER (G) NEC ARTICLE 310.16 EXISTING PL&P FEEDER NO 8 WIRE PROTECTED AT 400AMP |
OPEN |
12/21/2009 |
12/21/2009 |
|