Electrical Application Details for App #: Y147000
Premises: 2041 GRAND AVENUE BRONX BIN: 2114829     Block: 3206   Lot: 0
   
Application Completed and Certified

Filed: 55 W BURNSIDE AV Census Tract:   251 Health Area:  1520
55 Admin Area:   Y - BRONX Inspection Area:   F
BRONX, NY 10453 Community Board:   205
Related Job Number:    201009737
DOB Cross Street(s):   GRAND AVENUE,    HARRISON AVENUE
Status:   C - JOB IS SIGNED OFF 03/23/2012
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  06/11/2009 4:39 PM
Application Entered:   06/11/2009 Job Start Date:   08/20/2009
Last Change:   03/23/2012 Job End Date:   11/15/2009
Appointment Status:   
Last Inspection By:   HINDS EUGENE       On     03/12/2012      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011738 Licensee Name: WAYNE S LOCKER
Firm: 003702 Firm Name: ENOK ELECTRICAL CO LLC
Firm Phone: 718-361-9711  Firm Address: 47-36 36TH STREET LONG ISLAND CITY NY 11101 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
Total Fee:  $540.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: VERONA GREENLAND
Owner Business Name: MORRIS HEIGHTS HEALTH CTR
Authorized Representative:  VERONA GREENLAND
Relationship To Owner:   REP


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  4  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: C - CALL TO OFFICE 01/17/2012
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Y147000
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 11/30/2010 12/10/2010 GYM V (135) (7) Y
INSPECTION COMMENTS: V
 
(2) 12/29/2011 01/17/2012 KAS H X (30) (0) Y
INSPECTION COMMENTS: NO PROGRESS ON JOB/VIOLATION NOT REMOVED
 
(3) 02/06/2012 02/16/2012 EBA N (45) (0) Y
INSPECTION COMMENTS: NO SHOW
 
(4) 03/12/2012 03/23/2012 EHD C R (40) (0) Y
INSPECTION COMMENTS: C

OBJECTION FOR APPLICATION #: Y147000
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 16) DEFECTIVE LIGHTING FIXTURES ARE IN USE
BSMT/LIGHTS IN ELEVATOR PIT
RSLV 11/30/2010 12/29/2011 03/12/2012
 
002 ( 17) DEFECTIVE SWITCHES ARE IN USE
BSMT/LIGHTS IN ELEVATOR PIT
RSLV 11/30/2010 12/29/2011 03/12/2012
 
003 ( 18) DEFECTIVE RECEPTACLES ARE IN USE
BSMT/LIGHTS IN ELEVATOR PIT
RSLV 11/30/2010 12/29/2011 03/12/2012
 
004 ( 19) DEFECTIVE WIRING IS IN USE
BSMT/LIGHTS IN ELEVATOR PIT
RSLV 11/30/2010 12/29/2011 03/12/2012
 
005 ( 18) DEFECTIVE RECEPTACLES ARE IN USE
A-1FL RECEPT GFCI TOP OF ELEVATOR
RSLV 11/30/2010 12/29/2011 03/12/2012
 
006 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
BSMT-ELEVATOR MACHINE ROOM 30A DISC SWS CAB LIGHTS
RSLV 11/30/2010 12/29/2011 03/12/2012
 
007 ( 17) DEFECTIVE SWITCHES ARE IN USE
A-BSMT FUSES FOR CAB LIGHTS JUMPER WITH WIRES
RSLV 11/30/2010 12/29/2011 03/12/2012