| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
1 |
400 |
| D. 601 Up to 1200 AMPS |
3 |
800, 800, 1200 |
| E. Over 1200 AMPS |
1 |
1600 |
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
2 |
|
| B. Over #2 to 1/0 |
6 |
|
| C. Over 1/0 to 250 MCM |
8 |
|
| D. Over 250 MCM |
14 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
71 |
12CKT |
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
19 |
100, 100, & 17 @ 200 |
| D. 3 Phase Over 225 AMPS |
5 |
400, 400, 400, 800, 1200 |
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 1) |
SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER 1 SERVICE ENTRANCE NOT BONDED PROPERLY |
RSLV |
12/02/2010 |
12/02/2010 |
03/15/2011 |
| |
| 002 |
(999) |
OTHER 1F NOT PER ARTICLE 410.73G FIXTURES NOT DISCONNECTS |
RSLV |
12/02/2010 |
12/02/2010 |
03/15/2011 |
| |
| 003 |
(999) |
OTHER NOT PER ARTICLE 517.13A.13 EXAM OFFICE PATRNT CAR METAL RACEWAY |
RSLV |
12/02/2010 |
12/02/2010 |
03/15/2011 |
| |
| 004 |
(999) |
OTHER NOT PER DRAWING FIREPUMP AND JACKEY PUMP TAP |
RSLV |
12/02/2010 |
12/02/2010 |
03/15/2011 |
| |
| 005 |
(999) |
OTHER NOT PER DRAWING 800 S.S |
RSLV |
12/02/2010 |
12/02/2010 |
03/15/2011 |
| |
| 006 |
(999) |
OTHER BASEMENT ARTICLE 517.13A MENTAL REACEWAY IS NOT PROVIDED FOR PATIENT CARE AREA EXAM ROOM |
RSLV |
03/15/2011 |
03/15/2011 |
10/11/2011 |
| |
| 007 |
(999) |
OTHER (A) BASEMENT ARTICLE RECEPTACLE AR PATIENT BED LOCATION IS NOT HOSPITAL GRADE (SEE MANUFACTURE PATIENT BED) |
RSLV |
03/15/2011 |
03/15/2011 |
10/11/2011 |
| |
| 008 |
(999) |
OTHER ARTICLE 240.12 800A SERVICE SW FUSE USED NO COORDINATION WITH BREAKERS S.SW #3 REV 3 CALENDOAR NO 49486 |
RSLV |
03/15/2011 |
03/15/2011 |
10/11/2011 |