Electrical Application Details for App #: Y144413
Premises: 471 EAST TREMONT AVENUE BRONX BIN: 2115978     Block: 3043   Lot: 1
   
Application Completed and Certified

Filed: 1920 WASHINGTON AV Census Tract:   377 Health Area:  1700
BASEMENT & 1ST FLOOR Admin Area:   Y - BRONX Inspection Area:   I
BRONX, NY 10457 Community Board:   206
DOB Cross Street(s):   EAST TREMONT AVENUE,    EAST 178 STREET
Status:   C - JOB IS SIGNED OFF 05/08/2009
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  11/14/2008 1:51 PM
Application Entered:   11/14/2008 Job Start Date:   11/14/2008
Last Change:   05/08/2009 Job End Date:   01/30/2009
Appointment Status:   
Last Inspection By:   PETER CONTEY       On     04/23/2009      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 009873 Licensee Name: JOE MIDDLETON
Firm: 001933 Firm Name: NORWAY ELECTRIC CORP.
Firm Phone: 718-992-5500  Firm Address: 1205 JEROME AVENUE BRONX NY 10452 

Work Started or Filed by Others: YES
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $233.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: FOX Y GARCIA CONSTRUCTION
Authorized Representative:  BOBBY GARCIA
Relationship To Owner:   OWNER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  2  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  2  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL    30  15    30             
001    70  35    10  70             
Buildings Total 100  50    15  100                
Total Units : 265 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 04/13/2009
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Y144413
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 04/06/2009 04/13/2009 PC2 V (60) (4) Y
INSPECTION COMMENTS: VIOL
 
(2) 04/23/2009 04/30/2009 PC2 C R (65) (0) Y
INSPECTION COMMENTS: C

OBJECTION FOR APPLICATION #: Y144413
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
A)NEC ART 250.146.148 MCCABLE BRANCH CIRCUIT WIRING OUTLET BOXES & WIRING DEVICES NOT PROPERLY BONDED
RSLV 04/06/2009 04/06/2009 04/23/2009
 
002 (999) OTHER
B)NEC ART 250.24 A.J MCCABLE BONDING CONDUCTORS TERMINATED AT NEUTRAL BAR AT CIRCUIT BREAKER PANEL AFTER SERVICE SWITCH
RSLV 04/06/2009 04/06/2009 04/23/2009
 
003 (999) OTHER
C)NEC ART 210.63 GFGI RECEPTALE NOT PROVIDED TO SERVICE 4AC UNITSIN REAR YARD
RSLV 04/06/2009 04/06/2009 04/23/2009
 
004 (999) OTHER
D)NEC ART 356.10.1 OUTDOOR AC COMPRESSORS SEALTITE FOR BRANCH CIRCUITS EXCEEDS 6FT LONG
RSLV 04/06/2009 04/06/2009 04/23/2009