| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
5 |
1-100AMP |
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
5 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
1 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
5 |
12 CKT 1PHASE PNL |
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(999) |
OTHER (A) NEC ARTICLE 210.12.13 ARC FAULT BRANCH CIRCUIT PROTECTION NOT PROVIDED FOR BEDROOM OUTLETS LIGHTS AND AC OUTLETD 1ST -2ND,3RD FL APT |
RSLV |
11/12/2009 |
11/12/2009 |
12/16/2009 |
| |
| 002 |
(999) |
OTHER (B) NEC ARTICLE 210.8.6 KITCHEN COUNTER OUTLETS GFCI DOES NOT TRIP ON TEST 3RDFL APT ONLY |
RSLV |
11/12/2009 |
11/12/2009 |
12/16/2009 |
| |
| 003 |
(999) |
OTHER (C) NEC ARTICLE 210.8.A.1 BATHROOM OUTLET GFCI DOESNOT TRIP ON TESTCOMMERCIAL SPACE ONLY |
RSLV |
11/12/2009 |
11/12/2009 |
12/16/2009 |
| |
| 004 |
(999) |
OTHER (D) NEC ARTICLE 250.53.D.1 WATER METER BONDING JUMPER NOT PROVIDED |
RSLV |
11/12/2009 |
11/12/2009 |
12/16/2009 |
| |
| 005 |
(999) |
OTHER (E) NEC ARTCILE N.Y.C AMMENDMENT 356.10 NEW METALLIC SEALTITE USED TO PROVIDED POWER TO AC COMPRESSORS FOE COMMERICAL SPACE AND BASEMENT |
RSLV |
11/12/2009 |
11/12/2009 |
12/16/2009 |
| |
| 006 |
(999) |
OTHER (F) NEC ARTICLE 400.8 RUBBER CORD PROVIDING POWER TO AC AIR HANLDERS FOE COMMERICAL SPACE AND BASEMENT |
RSLV |
11/12/2009 |
11/12/2009 |
12/16/2009 |
| |
| 007 |
(999) |
OTHER (G) NEC ARTICLE 430.74 DICONNECT SWITH NOT PROVIDED FOE AIR HANLDERSFOR COMMERCAIL SPACE AND BASEMENT |
RSLV |
11/12/2009 |
11/12/2009 |
12/16/2009 |