Electrical Application Details for App #: Y142577
Premises: 712 EAST 214 STREET BRONX BIN: 2117623     Block: 4661   Lot: 12
   
Application Completed and Certified

Filed: 712 E 214 ST Census Tract:   380 Health Area:  0610
BASE, 1ST,2,3,4TH FLOORS Admin Area:   Y - BRONX Inspection Area:   L
BRONX, NY 10467 Community Board:   212
Related Job Number:    210009578
DOB Cross Street(s):   WHITE PLAINS ROAD,    HOLLAND AVENUE
Status:   C - JOB IS SIGNED OFF 01/14/2010
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  07/03/2008 3:55 PM
Application Entered:   07/03/2008 Job Start Date:   07/06/2008
Last Change:   01/14/2010 Job End Date:   08/06/2008
Appointment Status:   
Last Inspection By:   PETER CONTEY       On     12/16/2009      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011997 Licensee Name: CRAIG E SAMUELS
Firm: 003645 Firm Name: AMPERE ELECTRIC CORP
Firm Phone: 718-527-9324  Firm Address: 200-06 LINDEN BLVD ST. ALBANS NY 11412 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $343.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   E - Four Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: SAMMY CHUNASAMY
Owner Business Name: DCRA DEVELOPMENT
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  5  1-100AMP
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  5  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  5  12 CKT 1PHASE PNL
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total 60  100  12  50  60                
Total Units : 282 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 1 #4-Wire 0 #10-Wire 0
Existing Meters 5 + New Meters 0 - Removed Meters 0 = Total Meters 5

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 07/03/2008 Notice: 1 - FIRST NOTICE 11/24/2009
Power Issued: 07/03/2008 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Y142577
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 11/12/2009 11/24/2009 PC2 V E (45) (7) Y
INSPECTION COMMENTS: VIOALTION
 
(2) 12/16/2009 12/24/2009 PC2 C R E (30) (0) Y
INSPECTION COMMENTS: C

OBJECTION FOR APPLICATION #: Y142577
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(A) NEC ARTICLE 210.12.13 ARC FAULT BRANCH CIRCUIT PROTECTION NOT PROVIDED FOR BEDROOM OUTLETS LIGHTS AND AC OUTLETD 1ST -2ND,3RD FL APT
RSLV 11/12/2009 11/12/2009 12/16/2009
 
002 (999) OTHER
(B) NEC ARTICLE 210.8.6 KITCHEN COUNTER OUTLETS GFCI DOES NOT TRIP ON TEST 3RDFL APT ONLY
RSLV 11/12/2009 11/12/2009 12/16/2009
 
003 (999) OTHER
(C) NEC ARTICLE 210.8.A.1 BATHROOM OUTLET GFCI DOESNOT TRIP ON TESTCOMMERCIAL SPACE ONLY
RSLV 11/12/2009 11/12/2009 12/16/2009
 
004 (999) OTHER
(D) NEC ARTICLE 250.53.D.1 WATER METER BONDING JUMPER NOT PROVIDED
RSLV 11/12/2009 11/12/2009 12/16/2009
 
005 (999) OTHER
(E) NEC ARTCILE N.Y.C AMMENDMENT 356.10 NEW METALLIC SEALTITE USED TO PROVIDED POWER TO AC COMPRESSORS FOE COMMERICAL SPACE AND BASEMENT
RSLV 11/12/2009 11/12/2009 12/16/2009
 
006 (999) OTHER
(F) NEC ARTICLE 400.8 RUBBER CORD PROVIDING POWER TO AC AIR HANLDERS FOE COMMERICAL SPACE AND BASEMENT
RSLV 11/12/2009 11/12/2009 12/16/2009
 
007 (999) OTHER
(G) NEC ARTICLE 430.74 DICONNECT SWITH NOT PROVIDED FOE AIR HANLDERSFOR COMMERCAIL SPACE AND BASEMENT
RSLV 11/12/2009 11/12/2009 12/16/2009