BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Y142313
Premises: 2315 CRESTON AVENUE BRONX BIN: 2013890     Block: 3172   Lot: 32
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 2315 CRESTON AV Census Tract:   237.01 Health Area:  1600
EAST 183RD STREET Admin Area:   Y - BRONX Inspection Area:   F
BRONX, NY 10468 Community Board:   205
DOB Cross Street(s):   EAST 183 STREET,    FIELD PLACE
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  06/18/2008 10:05 AM
Application Entered:   06/18/2008 Job Start Date:   07/23/2008
Last Change:   08/22/2025 Job End Date:   04/24/2009
Appointment Status:   
Last Inspection By:   ASHMAN, K.       On     10/11/2011      
Field Disp:   H - NO PROGRESS ON JOB
Energize Recommendation:  
Objection Disposition:  Y - PARTLY REMOVED

License #: 011643 Licensee Name: MARK W BOBB
Firm: 003203 Firm Name: BOBTEK ELECTRICAL CORP.
Firm Phone: 718-763-2563  Firm Address: 934 EAST 51ST STREET BROOKLYN NY 11203 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
Total Fee:  $165.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: WES CANCEL
Owner Business Name: EKTO REALTY CORP.
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  1  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 12/10/2010
Power Issued: Response:  

Follow-Up:
Contractor's Comments:  DEVICE NUMBER 2P1973

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Y142313
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 11/30/2010 12/10/2010 GYM A (65) (4) Y
INSPECTION COMMENTS: VIOL
 
(2) 10/11/2011 10/26/2011 KAS H Y (45) (0) Y
INSPECTION COMMENTS: NO PROGRESS ON JOB

OBJECTION FOR APPLICATION #: Y142313
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
BSMT-NEC ART 620.85 NO GFCI ELEVATOR PIT
RSLV 11/30/2010 11/30/2010 10/11/2011
 
002 (999) OTHER
BSMT & ROOF/SEC 210.19 ELEVATOR MACHINE ROOM BR CKT WIRING LIGHTSSWS RECEPT #14 AWE USED NYC AMEN ROOF & BSMT ELEVATOR PIT
RSLV 11/30/2010 11/30/2010 10/11/2011
 
003 ( 25) ARMORED CABLES ARE NOT PROPERLY TERMINATED
ROOF/ELEVATOR MOTOR GRD CONDUCTOR
OPEN 11/30/2010 10/11/2011
 
004 ( 37) MOTOR DISCONNECT SWITCH HAS NOT BEEN PROVIDED
ROOF/BRANCH CIRCUIT WIRING ELEVATOR MACHINE ROOM
RSLV 11/30/2010 11/30/2010 10/11/2011



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order