BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Y142143
Premises: 915 SOUTHERN BOULEVARD BRONX BIN: 2005765     Block: 2723   Lot: 54
   
Application Completed and Certified

Filed: 919 SOUTHERN BLVD Census Tract:   89 Health Area:  3700
STREET Admin Area:   Y - BRONX Inspection Area:   C
BRONX, NY 10459 Community Board:   202
Special Place Name:   PLUMBING SUPPLYS
DOB Cross Street(s):   BARRETTO STREET,    EAST 163 STREET
Status:   C - JOB IS SIGNED OFF 05/26/2009
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  06/06/2008 10:16 AM
Application Entered:   06/06/2008 Job Start Date:   06/06/2008
Last Change:   05/26/2009 Job End Date:   09/01/2008
Appointment Status:   
Last Inspection By:   ASHMAN, K.       On     04/06/2009      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 009788 Licensee Name: VITO PROSCIA
Firm: 001179 Firm Name: PROSCIA ELECTL CONTRNG IN
Firm Phone: 718-357-9191  Firm Address: 141-07 20TH AVE.-SUITE 603 WHITESTONE NY 11357 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
5 - FIRE DAMAGE
6 - GENERAL WIRING
Total Fee:  $320.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   K - Store
Store / Other:   PLUMBING SUPPLY
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: PALACE PLUMBING
Authorized Representative:  SCOTT HARTMAN
Relationship To Owner:   OWNER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  1  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  3  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  3  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total 10  15  10  10              
Total Units : 51 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 1 #10-Wire 0
Existing Meters 1 + New Meters 1 - Removed Meters 1 = Total Meters 1

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 06/06/2008 Notice: 1 - FIRST NOTICE 03/16/2009
Power Issued: 06/06/2008 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Y142143
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 03/10/2009 03/16/2009 GYM V E (65) (7) Y
INSPECTION COMMENTS: VIOLATIONS
 
(2) 04/06/2009 04/07/2009 KAS C R E (40) (0) Y
INSPECTION COMMENTS: C

OBJECTION FOR APPLICATION #: Y142143
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
BASEMENT ARTICLE 250.28 200A SER SW NEUTRAL BAR IS NOT BONDED
RSLV 03/10/2009 03/10/2009 04/06/2009
 
002 (999) OTHER
(A) OUTDOOR ARTICLE 210.63 OUTLET IS NOT PROVIDED TO SERVICE A/C ORHEATING UNITS OUTSIDE
RSLV 03/10/2009 03/10/2009 04/06/2009
 
003 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
BASEMENT WATER MAIN GROUND NOT PROPERLY INSTALLED 200A SER SW
RSLV 03/10/2009 03/10/2009 04/06/2009
 
004 ( 24) ARMORED CABLES ARE NOT PROPERLY SECURED
OUTSIDE ARMORED CABLES
RSLV 03/10/2009 03/10/2009 04/06/2009
 
005 ( 25) ARMORED CABLES ARE NOT PROPERLY TERMINATED
OUTSIDE ARMORED CABLES
RSLV 03/10/2009 03/10/2009 04/06/2009
 
006 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
OUTSIDE ARMORED CABLES
RSLV 03/10/2009 03/10/2009 04/06/2009
 
007 (999) OTHER
(B) ARTICLE 410.74 LUMINAIR DISCONNECT PUSH SW NOT PROVIDED
RSLV 03/10/2009 03/10/2009 04/06/2009



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.