BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Y141993
Premises: 1995 CRESTON AVENUE BRONX BIN: 2007653     Block: 2807   Lot: 16
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 1995 CRESTON AV Census Tract:   241 Health Area:  1600
O/D Admin Area:   Y - BRONX Inspection Area:   F
BRONX, NY 10453 Community Board:   205
DOB Cross Street(s):   EAST 178 STREET,    EAST 179 STREET
Status:   C - JOB IS SIGNED OFF 10/09/2019
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  05/29/2008 3:21 PM
Application Entered:   05/29/2008 Job Start Date:   06/05/2008
Last Change:   10/09/2019 Job End Date:   07/05/2008
Appointment Status:   
Last Inspection By:   RICHARD REED       On     10/09/2019      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011917 Licensee Name: ALTAF H SYED-NAQVI
Firm: 003528 Firm Name: ALSON ELEC'L CONTR. INC
Firm Phone: 718-435-1677  Firm Address: 1253 ROCKAWAY AVENUE BROOKLYN NY 11236 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
2 - TEMPORARY CONSTRUCTION
9 - OTHER
Total Fee:  $40.00
Other Work:   S. WALK SHED LIGHTING
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   Z - Other
Store / Other:   C1-WALK UP APTS.
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: BALBIR SINGH
Owner Business Name: B&S RESTORATION INC
Authorized Representative:  BALBIR SINGH
Relationship To Owner:   CONTRACTOR - A


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                       
Total Units : 8 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 10/01/2019
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  INSTALLING TEMPORARY LIGHTING UNDER SIDE WALK SHED BRIDGE. 60 L.F.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Y141993
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 10/01/2019 10/01/2019 RDY V (30) (3)
INSPECTION COMMENTS: INSPECTION FAILED SEE 3 OBJECTIONS.
 
(2) 10/09/2019 10/09/2019 RDY C R (4) (0)
INSPECTION COMMENTS: INSPECTION PASSED. NEW APPLICATION SUPERSEDES THIS APPLICATION X00045344 OK TO PASS.

OBJECTION FOR APPLICATION #: Y141993
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (138) METAL RACEWAYS AND ENCLOSURES DO NOT HAVE ELECTRICAL CONTINUITY
(OPEN SPACE) 3/4 IMC HAS BEEN DISCONNECTED IN THE MIDDLE OF PIPE RUN
RSLV 10/01/2019 10/01/2019 10/09/2019
 
002 (999) OTHER
(OPEN SPACE) NO GROUND ROD INSTALLED 250.53(D)2
RSLV 10/01/2019 10/01/2019 10/09/2019
 
003 (999) OTHER
(OPEN SPACE) DEFECTIVE LAMPS IN USE 590.8 1-7
RSLV 10/01/2019 10/01/2019 10/09/2019



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.