Electrical Application Details for App #: Y141072
Premises: 3725 BLACKSTONE AVENUE BRONX BIN: 2085794     Block: 5907   Lot: 348
   
Application Completed and Certified

Filed: 3725 BLACKSTONE AV Census Tract:   307 Health Area:  0100
MOTOR ROOM Admin Area:   Y - BRONX Inspection Area:   H
BRONX, NY 10463 Community Board:   208
DOB Cross Street(s):   WEST 238 STREET,    WEST 239 STREET
Status:   C - JOB IS SIGNED OFF 03/29/2010
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  03/26/2008 12:01 PM
Application Entered:   03/26/2008 Job Start Date:   03/28/2008
Last Change:   03/29/2010 Job End Date:   01/23/2009
Appointment Status:   
Last Inspection By:   ASHMAN, K.       On     03/16/2010      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011165 Licensee Name: JAMES KRUGER
Firm: 002557 Firm Name: VINTAGE ELEC. SERVICE INC
Firm Phone: 718-338-3910  Firm Address: 2812 HARWAY AVE BROOKLYN NY 11214 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
Total Fee:  $165.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: STAFFARD GARSON PROPERTIE
Authorized Representative:  STEPHEN RUOCCO
Relationship To Owner:   EXPEDITOR


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  1  7 STORIES
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: C - CALL TO OFFICE 02/09/2010
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  #1013 REPLACE SAFETY SWITCH, CONTROLLER, SHAFT AND CAR WIRING FOR 2P4113

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Y141072
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 12/02/2009 12/08/2009 PC2 V (60) (4)
INSPECTION COMMENTS: VIOLATION
 
(2) 02/03/2010 02/09/2010 MIR H X (30) (0) Y
INSPECTION COMMENTS: O
 
(3) 03/16/2010 03/29/2010 KAS C R (60) (0) Y
INSPECTION COMMENTS: C

OBJECTION FOR APPLICATION #: Y141072
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(A) NEC ARTICLE 358.30 EMT CONDUIT FROM CONTROLLOR TO MOTOR NOT SUPPORTED PROPERLY
RSLV 12/02/2009 02/03/2010 03/16/2010
 
002 (999) OTHER
(B) NEC ARTICLE 250.24.S.5 NUETRAL BONDED IN CAB LIGHTING DISCONNECT SWITCH
RSLV 12/02/2009 02/03/2010 03/16/2010
 
003 (999) OTHER
(C) NEC ARTICLE 408.41 CABLE LIGHTING DISCONNECT SWITCH MULTI WIRE TERMONATED AR SINGLE LUG
RSLV 12/02/2009 02/03/2010 03/16/2010
 
004 (999) OTHER
(D) NEC ARTICLE 210.4 D AND 210.5 POWER CONDUCTORS FROM MAIN DISCONNECT TO CONTROLLOR AND FROM CONTROOLO TO MOTOR COLOR WHITE
RSLV 12/02/2009 02/03/2010 03/16/2010



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.