BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Y140456
Premises: 5661 RIVERDALE AVENUE BRONX BIN: 2086317     Block: 5953   Lot: 1
   
Application Completed and Certified

Filed: 5661 RIVERDALE AV Census Tract:   323 Health Area:  0100
PARKING LOT Admin Area:   Y - BRONX Inspection Area:   H
BRONX, NY 10471 Community Board:   208
DOB Cross Street(s):   WEST 256 STREET,    WEST 258 STREET
Status:   C - JOB IS SIGNED OFF 09/29/2008
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  02/19/2008 9:57 AM
Application Entered:   02/19/2008 Job Start Date:   02/27/2008
Last Change:   09/29/2008 Job End Date:   03/15/2008
Appointment Status:   
Last Inspection By:   PETER CONTEY       On     09/22/2008      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 010133 Licensee Name: JOHN MUSTARO
Firm: 001167 Firm Name: POLYPHASE ELEC'L CONTR'S.
Firm Phone: 718-449-1003  Firm Address: 2201 NEPTUNE AVENUE BROOKLYN NY 11224 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $78.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   Z - Other
Store / Other:   SHOPPING CENTER
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: NAFTALE BRAUN
Owner Business Name: RIVERDALE HOLDING
Authorized Representative:  NAFTALE BRAUN
Relationship To Owner:   PARTNER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  1  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  #3 THHN
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  3 WIRE 8 CIRCUITS
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 1 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 1 - Removed Meters 0 = Total Meters 1

Power Auth Flag: K - CANCELLED Objection Flag:
Power Requested: 02/19/2008 Notice: 1 - FIRST NOTICE 09/08/2008
Power Issued: 02/19/2008 Response: V - OBJ WAS REMOVED 08/20/2008

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Y140456
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/25/2008 07/28/2008 PC2 Z (0) (0)
INSPECTION COMMENTS: APPOINMENT CANCELLED DUE TO INSPECTOR'S CAR BEING REPAIRED
 
(2) 08/04/2008 08/08/2008 KAS A B (35) (2) Y
INSPECTION COMMENTS: VIOLATION
 
(3) 09/02/2008 09/08/2008 PC2 A R E (45) (1) Y
INSPECTION COMMENTS: V
 
(4) 09/22/2008 09/29/2008 PC2 C R E (45) (0) Y
INSPECTION COMMENTS: CERT

OBJECTION FOR APPLICATION #: Y140456
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
OUTSIDE SERVICE SWITCH NOT BOLTED DOWN - MAIN. 408.36F
RSLV 08/04/2008 08/04/2008 09/02/2008
 
002 (999) OTHER
OUTSIDE - SIGNE E. MANUFACTURER INFORMATION IS NOT PROVIDED 600.4
RSLV 08/04/2008 08/04/2008 09/02/2008
 
003 (999) OTHER
A)NEC ARTICLE 250.53.B. 2 GROUND RODS PROVIDED FOR GROUNDING ELEC.SYSTEM. NO WATER MAIN AVAILABLE. RODS NOT MIN SPACING OF 6FT APART
RSLV 09/02/2008 09/02/2008 09/22/2008



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order