BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Y140291
Premises: 217 BROOK AVENUE BRONX BIN: 2097015     Block: 2265   Lot: 1
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 217 BROOK AV Census Tract:   25 Health Area:  4500
TO 229 BROOK AVE Admin Area:   Y - BRONX Inspection Area:   A
BRONX, NY 10454 Community Board:   201
DOB Cross Street(s):   EAST 137 STREET,    EAST 138 STREET
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   02/06/2008 Job Start Date:   02/06/2008
Last Change:   08/22/2025 Job End Date:   05/30/2008
Appointment Status:   
Last Inspection By:   JOFFRE PENA       On     12/28/2016      
Field Disp:   J - JOB IN PROGRESS
Energize Recommendation:  
Objection Disposition:  

License #: 012050 Licensee Name: DREW ROMANELLO
Firm: 003738 Firm Name: ROMCON ELECTRIC, INC
Firm Phone: 718-401-2112  Firm Address: 470 AUSTIN PLACE BRONX NY 10455 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $877.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   K - Store
Store / Other:   X
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: ROBERT MCGIVNEY
Owner Business Name: 217-229 BROOK LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  1  
C. 201 Up to 600 AMPS  3  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  4  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  3  
D. Over 250 MCM  3  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total 22  40    22              
Total Units : 98 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 5 #10-Wire 2
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 02/06/2008 Notice:  
Power Issued: 02/06/2008 Response:  

Follow-Up:
Contractor's Comments:  STORE,1,2FL

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Y140291
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 12/28/2016 12/28/2016 JRP J (50) (0) Y
INSPECTION COMMENTS: CONTRACTOR NOT READY FOR INSPECTION.




If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back