Electrical Application Details for App #: Y140128
Premises: 95 WEST 195 STREET BRONX BIN: 2015298     Block: 3249   Lot: 1
   
Application Completed and Certified

Filed: 95 W 195 ST Census Tract:   267 Health Area:  0320
SIDEWALK SHED Admin Area:   Y - BRONX Inspection Area:   F
BRONX, NY 10468 Community Board:   208
DOB Cross Street(s):   RESERVOIR AVENUE,    UNIVERSITY AVENUE
Status:   C - JOB IS SIGNED OFF 12/05/2012
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  01/28/2008 4:36 PM
Application Entered:   01/28/2008 Job Start Date:   01/29/2008
Last Change:   12/05/2012 Job End Date:   03/30/2008
Appointment Status:   
Last Inspection By:   BANYA, E       On     10/25/2012      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010985 Licensee Name: LINDEN J TUDOR
Firm: 002700 Firm Name: LINTECH ELECTRIC, INC
Firm Phone: 718-941-3766  Firm Address: 3006 TILDEN AVENUE BROOKLYN NY 11226 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
9 - OTHER
Total Fee:  $43.00
Other Work:   SIDEWALK SHED
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   Z - Other
Store / Other:   SIDEWALK SHED
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: NABEEL KHAN
Owner Business Name: ASAP QUALITY CONSTRUCTION
Authorized Representative:  NABEEL KHAN
Relationship To Owner:   OWNER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total         22                
Total Units : 22 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 07/11/2008
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  INSTALLING TEMPORARY LIGHTING UNDER SIDEWALK SHED

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Y140128
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/08/2008 07/11/2008 GYM A (30) (6)
INSPECTION COMMENTS: VIOLATION
 
(2) 10/25/2012 11/03/2012 EBA C R (20) (0) Y
INSPECTION COMMENTS: C

OBJECTION FOR APPLICATION #: Y140128
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
OUTDOOR - FEED TO SHED
RSLV 07/08/2008 07/08/2008 10/25/2012
 
002 (999) OTHER
A - OUTDOOR - NO G.F.C.I PROVIDED
RSLV 07/08/2008 07/08/2008 10/25/2012
 
003 (999) OTHER
B- OUTDOOR - EMT SHALL NOT BE USED OUTSIDE
RSLV 07/08/2008 07/08/2008 10/25/2012
 
004 (999) OTHER
C - OUTDOOR -SYSTEM IS NOT GROUNDED
RSLV 07/08/2008 07/08/2008 10/25/2012
 
005 ( 25) ARMORED CABLES ARE NOT PROPERLY TERMINATED
OUTDOOR - FEED TO SHED SWB LTG
RSLV 07/08/2008 07/08/2008 10/25/2012
 
006 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
OUTDOOR - FEED TO SHED SWB LTG
RSLV 07/08/2008 07/08/2008 10/25/2012