| BUILDING OVERVIEW |
Are Feeders Being Installed? : No |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
1 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(999) |
OTHER (ALL FLOORS)A)ART 620.85-SWITCH & LIGHTSING OTLT & GFGI RECEP NOT PROVIDED IN ELEV MTOR RM |
RSLV |
09/25/2008 |
10/05/2010 |
12/13/2017 |
| |
| 002 |
(999) |
OTHER (ALL FLOORS)B)ART 110.14 #6WIRE AT LOADS OF ELEVATOR DISCONECT SWITCH NOT PROVIDED WITH APPROVED LUGS |
RSLV |
09/25/2008 |
10/05/2010 |
12/13/2017 |
| |
| 003 |
(999) |
OTHER (ALL FLOORS)C)ART 358.30 EMT FROM DISCONNECT SWITCH TO CONTROLL & FROM CONTROLLOR TO MOTOR NOT SUPPORTED |
RSLV |
09/25/2008 |
10/05/2010 |
12/13/2017 |
| |
| 004 |
(999) |
OTHER (ALL FLOORS)D)ART 620.81-82 FEEDER & MOTOR CIRCUIT CONDUITS NOT TERMINATED WITHAPPROVED FTTINGS |
RSLV |
09/25/2008 |
10/05/2010 |
12/13/2017 |
| |
| 005 |
(999) |
OTHER (ALL FLOORS)E)ART 376.1 CONTRO WIRING THRU NOT TEDRM TO CONTROLLOR WITH APPROVED FITTINGS |
RSLV |
09/25/2008 |
10/05/2010 |
11/09/2018 |
| |
| 006 |
(999) |
OTHER (ALL FLOORS)F)ART 348.6 CONDUITS & GREEN FIELD THRU OUT SHAFT NOT TERMINATED WITH APPROVED FITTINGS |
RSLV |
09/25/2008 |
10/05/2010 |
11/09/2018 |
| |
| 007 |
(999) |
OTHER (ALL FLOORS)G)ART 620.22B CAR LIGHTING NOT PROVIDED WITH DEDICATED BRANCH CIRCU |
RSLV |
09/25/2008 |
10/05/2010 |
12/13/2017 |
| |
| 008 |
(999) |
OTHER (BASEMENT) PIT LIGHT AND GFCI ON THE SAME CIRCUIT 620.24 |
RSLV |
12/13/2017 |
12/13/2017 |
11/09/2018 |
| |
| 009 |
( 34) |
KNOCKOUTS ARE NOT CLOSED IN PANEL BOX (ROOF) MOTOR DISCONNECT KO MISSING |
RSLV |
12/13/2017 |
12/13/2017 |
11/09/2018 |
| |
| 010 |
( 7) |
EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT) (ROOF) MOTOR ROOM EMT NOT SUPPORTED |
RSLV |
12/13/2017 |
12/13/2017 |
11/09/2018 |