Electrical Application Details for App #: Y138917
Premises: 2870 MARION AVENUE BRONX BIN: 2016565     Block: 3284   Lot: 57
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 2870 MARION AV Census Tract:   407.02 Health Area:  0420
BASEMENT Admin Area:   Y - BRONX Inspection Area:   H
BRONX, NY 10458 Community Board:   207
DOB Cross Street(s):   EAST 199 STREET,    BEDFORD PARK BOULEVARD
Status:   C - JOB IS SIGNED OFF 11/09/2018
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  10/26/2007 11:57 AM
Application Entered:   10/26/2007 Job Start Date:   10/31/2007
Last Change:   11/09/2018 Job End Date:   06/26/2008
Appointment Status:   
Last Inspection By:   RICHARD REED       On     11/09/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010725 Licensee Name: ALDO BLASKOVIC
Firm: 001917 Firm Name: BLASKO ELECT'L CONTRS INC
Firm Phone: 718-784-7525  Firm Address: 36-38 35TH STREET LONG ISLAND CITY NY 11106 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
Total Fee:  $165.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: WES CANCEL
Owner Business Name: SCHUR MANAGEMENT
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  1  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 12/14/2017
Power Issued: Response: W - OBJ TO BE REMOVED 10/16/2008

Follow-Up: K - (CLOSED)
Contractor's Comments:  DEVICE NUMBER 2P1543

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Y138917
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 09/25/2008 10/07/2008 PC2 V (45) (7) Y
INSPECTION COMMENTS: VIOL
 
(2) 10/05/2010 10/19/2010 PC2 H X (45) (0) Y
INSPECTION COMMENTS: VIOL NOT REMOVED AT THIS TIME
 
(3) 12/13/2017 12/14/2017 GIG V Y (58) (3)
INSPECTION COMMENTS: INSPECTION FAILED
 
(4) 11/09/2018 11/09/2018 RDY C R (32) (0)
INSPECTION COMMENTS: INSPECTION PASSED OBJECTIONS REMOVED.

OBJECTION FOR APPLICATION #: Y138917
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(ALL FLOORS)A)ART 620.85-SWITCH & LIGHTSING OTLT & GFGI RECEP NOT PROVIDED IN ELEV MTOR RM
RSLV 09/25/2008 10/05/2010 12/13/2017
 
002 (999) OTHER
(ALL FLOORS)B)ART 110.14 #6WIRE AT LOADS OF ELEVATOR DISCONECT SWITCH NOT PROVIDED WITH APPROVED LUGS
RSLV 09/25/2008 10/05/2010 12/13/2017
 
003 (999) OTHER
(ALL FLOORS)C)ART 358.30 EMT FROM DISCONNECT SWITCH TO CONTROLL & FROM CONTROLLOR TO MOTOR NOT SUPPORTED
RSLV 09/25/2008 10/05/2010 12/13/2017
 
004 (999) OTHER
(ALL FLOORS)D)ART 620.81-82 FEEDER & MOTOR CIRCUIT CONDUITS NOT TERMINATED WITHAPPROVED FTTINGS
RSLV 09/25/2008 10/05/2010 12/13/2017
 
005 (999) OTHER
(ALL FLOORS)E)ART 376.1 CONTRO WIRING THRU NOT TEDRM TO CONTROLLOR WITH APPROVED FITTINGS
RSLV 09/25/2008 10/05/2010 11/09/2018
 
006 (999) OTHER
(ALL FLOORS)F)ART 348.6 CONDUITS & GREEN FIELD THRU OUT SHAFT NOT TERMINATED WITH APPROVED FITTINGS
RSLV 09/25/2008 10/05/2010 11/09/2018
 
007 (999) OTHER
(ALL FLOORS)G)ART 620.22B CAR LIGHTING NOT PROVIDED WITH DEDICATED BRANCH CIRCU
RSLV 09/25/2008 10/05/2010 12/13/2017
 
008 (999) OTHER
(BASEMENT) PIT LIGHT AND GFCI ON THE SAME CIRCUIT 620.24
RSLV 12/13/2017 12/13/2017 11/09/2018
 
009 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
(ROOF) MOTOR DISCONNECT KO MISSING
RSLV 12/13/2017 12/13/2017 11/09/2018
 
010 ( 7) EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT)
(ROOF) MOTOR ROOM EMT NOT SUPPORTED
RSLV 12/13/2017 12/13/2017 11/09/2018