BIS Menu  |  DOB Violations  |  Elevators  |  Electrical Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Y137851
Premises: 922 SIMPSON STREET BRONX BIN: 2116211     Block: 2723   Lot: 33
   
Application Completed and Certified

Filed: 928 SIMPSON ST Census Tract:   89 Health Area:  3700
928 SIMPSON STREET Admin Area:   Y - BRONX Inspection Area:   C
BRONX, NY 10459 Community Board:   202
Special Place Name:   BRONX STUDIO
Related Job Number:    200897066
DOB Cross Street(s):   BARRETTO STREET,    EAST 163 STREET
Status:   C - JOB IS SIGNED OFF 10/29/2010
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  08/17/2007 1:24 PM
Application Entered:   08/17/2007 Job Start Date:   08/17/2007
Last Change:   10/29/2010 Job End Date:   12/23/2009
Appointment Status:   
Last Inspection By:   GARY MCCALLA       On     10/05/2010      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011767 Licensee Name: CHRISTOPHER TOTARO
Firm: 001449 Firm Name: TRU-VAL ELECTRIC CORP.
Firm Phone: 718-652-5050  Firm Address: 2550 PARK AVENUE BRONX NY 10451 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $5,040.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   W - School
Special Cert Approval:  
Advisory Board Approval:   REQUIRED
Advisory Board Categories:      K - 1000 KVA SERVICE                            
Advisory Board Approval #:        Submittal #:   
Owner / Occup: CRAIG COLLINS
Owner Business Name: NYC SCA
Authorized Representative:  CRAIG COLLINS
Relationship To Owner:   CHIEF PROJECT OFFICER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  1  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  1  
E. Over 1200 AMPS  2  2-2500AMP
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  4  #2,#4
B. Over #2 to 1/0  4  #1/0
C. Over 1/0 to 250 MCM  13  #3/0,#4/0,#250MCM
D. Over 250 MCM  47  #350MCM, #500MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  13  60A,100A,125A
D. 3 Phase Over 225 AMPS  23  400A,225A
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total 1312  995    216       300           
Total Units : 2823 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 1
Existing Meters 1 + New Meters 1 - Removed Meters 1 = Total Meters 1

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 08/17/2007 Notice: C - CALL TO OFFICE 08/19/2010
Power Issued: 08/17/2007 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Y137851
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 08/06/2009 08/19/2009 GYM V E (90) (5) Y
INSPECTION COMMENTS: VIOL
 
(2) 10/06/2009 10/13/2009 GYM H X E (60) (0) Y
INSPECTION COMMENTS: C
 
(3) 10/06/2009 10/13/2009 GYM H X E (60) (0) Y
INSPECTION COMMENTS: C
 
(4) 03/16/2010 03/29/2010 GYM A R E (105) (4) Y
INSPECTION COMMENTS: V
 
(5) 04/27/2010 05/04/2010 GYM J Y E (55) (0) Y
INSPECTION COMMENTS: C
 
(6) 05/19/2010 06/01/2010 GYM J Y E (105) (0) Y
INSPECTION COMMENTS: NR-#99,#4
 
(7) 08/16/2010 08/19/2010 GYM J X (115) (0) Y
INSPECTION COMMENTS: N/R #4 & #99
 
(8) 10/05/2010 10/19/2010 GYM C R E (55) (0) Y
INSPECTION COMMENTS: C

OBJECTION FOR APPLICATION #: Y137851
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 4) SERVICE IN EXCESS OF 1000KVA HAS NOT BEEN SUBMITTED FOR APPROVAL
BSMT/LAYOUT IS NOT AS PER DRAWING DOOR MDP PANELS #5/#7/#8
RSLV 08/06/2009 10/06/2009 03/16/2010
 
002 (999) OTHER
BSMT/ART 110.26 FIRE RATED DOOR WITH PANIC HARDWARE NOT PROVIDED
RSLV 08/06/2009 10/06/2009 03/16/2010
 
003 (999) OTHER
A)BSMT/ ART.695.4 FIRE PUMP SER SW IS NOT PAINTED RED
RSLV 08/06/2009 10/06/2009 03/16/2010
 
004 (999) OTHER
B)BSMT ART 695.4 FIRE PUMP SER SW IS NOT REMOTE
RSLV 08/06/2009 10/06/2009 03/16/2010
 
005 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
ENTIRE/METAL BOXEX WITH MC CABLES NOT GROUNDED
RSLV 08/06/2009 10/06/2009 03/16/2010
 
006 (999) OTHER
ENTIRE NEC ARTICLE 250.146.148 ALL AREAS WITH MC CABLE BRACK CIRCUITS WIRING OUTLET BOXES ARE BONDED
RSLV 03/16/2010 08/16/2010 10/05/2010
 
007 (999) OTHER
BASEMENT NEC ARTCILE 695.4B4 FIRE PIUMP SER SW NOT MARKED
RSLV 03/16/2010 03/16/2010 04/27/2010
 
008 ( 4) SERVICE IN EXCESS OF 1000KVA HAS NOT BEEN SUBMITTED FOR APPROVAL
BASEMENT SIEMENS SB3 2500A SWBD DP-B VB/HCP DISTRIBUTION SECTION ISNOT AS PER DRAWINGS
RSLV 03/16/2010 08/16/2010 10/05/2010
 
009 ( 4) SERVICE IN EXCESS OF 1000KVA HAS NOT BEEN SUBMITTED FOR APPROVAL
(A) BASEMENT 600 A APTS-1 AUTOMATIC TRANSFER SWITCH IS NOT AS PER DRAWINGS
RSLV 03/16/2010 04/27/2010 05/19/2010