| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
1 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
1 |
|
| E. Over 1200 AMPS |
2 |
2-2500AMP |
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
4 |
#2,#4 |
| B. Over #2 to 1/0 |
4 |
#1/0 |
| C. Over 1/0 to 250 MCM |
13 |
#3/0,#4/0,#250MCM |
| D. Over 250 MCM |
47 |
#350MCM, #500MCM |
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
13 |
60A,100A,125A |
| D. 3 Phase Over 225 AMPS |
23 |
400A,225A |
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 4) |
SERVICE IN EXCESS OF 1000KVA HAS NOT BEEN SUBMITTED FOR APPROVAL BSMT/LAYOUT IS NOT AS PER DRAWING DOOR MDP PANELS #5/#7/#8 |
RSLV |
08/06/2009 |
10/06/2009 |
03/16/2010 |
| |
| 002 |
(999) |
OTHER BSMT/ART 110.26 FIRE RATED DOOR WITH PANIC HARDWARE NOT PROVIDED |
RSLV |
08/06/2009 |
10/06/2009 |
03/16/2010 |
| |
| 003 |
(999) |
OTHER A)BSMT/ ART.695.4 FIRE PUMP SER SW IS NOT PAINTED RED |
RSLV |
08/06/2009 |
10/06/2009 |
03/16/2010 |
| |
| 004 |
(999) |
OTHER B)BSMT ART 695.4 FIRE PUMP SER SW IS NOT REMOTE |
RSLV |
08/06/2009 |
10/06/2009 |
03/16/2010 |
| |
| 005 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED ENTIRE/METAL BOXEX WITH MC CABLES NOT GROUNDED |
RSLV |
08/06/2009 |
10/06/2009 |
03/16/2010 |
| |
| 006 |
(999) |
OTHER ENTIRE NEC ARTICLE 250.146.148 ALL AREAS WITH MC CABLE BRACK CIRCUITS WIRING OUTLET BOXES ARE BONDED |
RSLV |
03/16/2010 |
08/16/2010 |
10/05/2010 |
| |
| 007 |
(999) |
OTHER BASEMENT NEC ARTCILE 695.4B4 FIRE PIUMP SER SW NOT MARKED |
RSLV |
03/16/2010 |
03/16/2010 |
04/27/2010 |
| |
| 008 |
( 4) |
SERVICE IN EXCESS OF 1000KVA HAS NOT BEEN SUBMITTED FOR APPROVAL BASEMENT SIEMENS SB3 2500A SWBD DP-B VB/HCP DISTRIBUTION SECTION ISNOT AS PER DRAWINGS |
RSLV |
03/16/2010 |
08/16/2010 |
10/05/2010 |
| |
| 009 |
( 4) |
SERVICE IN EXCESS OF 1000KVA HAS NOT BEEN SUBMITTED FOR APPROVAL (A) BASEMENT 600 A APTS-1 AUTOMATIC TRANSFER SWITCH IS NOT AS PER DRAWINGS |
RSLV |
03/16/2010 |
04/27/2010 |
05/19/2010 |