BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Y091554
Premises: 453 EAST 160 STREET BRONX BIN: 2001500     Block: 2382   Lot: 39
   

Filed: 453 E 160 ST Census Tract:   141 Health Area:  3400
9909843 14 24 28 29 33 Admin Area:   Y - BRONX Inspection Area:   C
BRONX, NY 10451 Community Board:   203
DOB Cross Street(s):   ELTON AVENUE,    WASHINGTON AVENUE
Status:   K - CLOSED/CANCELLED 12/02/2005
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   12/16/1998 Job Start Date:   12/03/1998
Last Change:   12/02/2005 Job End Date:   12/31/1998
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   ASHMAN, K.       On     12/01/2005      
Field Disp:   K - OK TO CANCEL
Energize Recommendation:  
Objection Disposition:  

License #: 011159 Licensee Name: BARRY KAPLOWITZ
Firm: 000399 Firm Name: DELTEX ELECTRICAL CONT. I
Firm Phone: 718-851-9220  Firm Address: 1027 MCDONALD AVENUE BROOKLYN NY 11230 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $34.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:  
Owner / Occup:
Owner Business Name: HPD
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total 15  44  15  30                
Total Units : 108 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice:  
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  APARTMENTS

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Y091554
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 11/29/2005 12/01/2005 MIR K (1) (0)
INSPECTION COMMENTS: SEE GUT REHAB Y125963
 
(2) 12/01/2005 12/02/2005 KAS K (1) (0)
INSPECTION COMMENTS: REMOVE BEFORE BEC INPS SEE#Y125969




If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order