BIS Menu  |  Pre-BIS PA CO Query By Bin  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: R154371
Premises: 75 VANDERBILT AVENUE STATEN ISLAND BIN: 5106863     Block: 534   Lot: 1
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 75 VANDERBILT AV Census Tract:   27 Health Area:  0500
3RD FLOOR K WING Admin Area:   R - STATEN ISLAND Inspection Area:   A
STATEN IS, NY 10304 Community Board:   501
DOB Cross Street(s):   ERRINGTON PLACE,    TALBOT PLACE
Status:   C - JOB IS SIGNED OFF 02/22/2018
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  11/08/2017 3:16 PM
Application Entered:   11/08/2017 Job Start Date:   11/10/2017
Last Change:   02/22/2018 Job End Date:   10/12/2018
Appointment Status:   
Last Inspection By:   TREJO, JORGE       On     02/21/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012475 Licensee Name: YEHOSHUA H GREENFELD
Firm: 004283 Firm Name: GREEN STAR ELECTL CONT IN
Firm Phone: 718-643-1500  Firm Address: 21 HERKIMER PLACE BROOKLYN NY 11216 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
7 - HVAC WIRING
T - TEMPORARY LIGHT & POWER
Total Fee:  $393.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: GROUP ONE70
Owner Business Name: ONE 70
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  1  SET #2
C. Over 1/0 to 250 MCM  2  SET 3 ORT
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  3  2-200 AMP 1-100 AMP
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
003    125  60    15  125  20         
Buildings Total 125  60    15  125     20           
Total Units : 345 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 02/15/2018
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: R154371
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/09/2018 02/09/2018 JTE N (30) (0) Y
INSPECTION COMMENTS: CONTRACTOR NO SHOW
 
(2) 02/14/2018 02/15/2018 OSZ V (60) (6)
INSPECTION COMMENTS: CORRECT OBJECTIONS.
 
(3) 02/21/2018 02/22/2018 JTE C R (50) (0)
INSPECTION COMMENTS: INSPECTION PASS

OBJECTION FOR APPLICATION #: R154371
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(FLOOR: 003)HANDLE TIE NEED FOR SHARED CKTS IN SMALL 200 AMP PANEL. 210.4(B)
RSLV 02/14/2018 02/14/2018 02/21/2018
 
002 (999) OTHER
(FLOOR: 003)WHITE WIRE USED AT BREAKER IN SMALL 200 AMP PANEL. ART 210.5(C)
RSLV 02/14/2018 02/14/2018 02/21/2018
 
003 (999) OTHER
(FLOOR: 003)LIGHTING FIXTURES OVER FRONT DESK ARE NOT PROPERLY GROUNDED. AMEND.110.2()A
RSLV 02/14/2018 02/14/2018 02/21/2018
 
004 (999) OTHER
(ALL FLOORS)NO BONDING HAS BEEN PROVIDED FOR 480V SERVICE SWITCHES AND PANELS.ART. 250.97
RSLV 02/14/2018 02/14/2018 02/21/2018
 
005 (123) SERVICE DISCONNECTS ARE NOT PROPERLY GROUPED/LABELED
(BASEMENT)SERVICE DISCONNECTS FEEDING SUBPANELS ARE NOT PROPERLY MARKED. ART.230.72(A)
RSLV 02/14/2018 02/14/2018 02/21/2018
 
006 (999) OTHER
(ROOF) AC DISCONNECTS NOT LABELED. ART. 110.22(A)
RSLV 02/14/2018 02/14/2018 02/21/2018



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Pre-BIS PA CO Query By Bin  |  Electrical Inspection Work Order  |  Back