BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: R153713
Premises: 75 VANDERBILT AVENUE STATEN ISLAND BIN: 5106863     Block: 534   Lot: 1
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 75 VANDERBILT AVE. Census Tract:   27 Health Area:  0500
6TH FLOOR Admin Area:   R - STATEN ISLAND Inspection Area:   A
STATEN IS, NY 10304 Community Board:   501
DOB Cross Street(s):   ERRINGTON PLACE,    TALBOT PLACE
Status:   C - JOB IS SIGNED OFF 03/09/2018
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  09/18/2017 2:56 PM
Application Entered:   09/18/2017 Job Start Date:   09/18/2017
Last Change:   03/09/2018 Job End Date:   09/17/2018
Appointment Status:   
Last Inspection By:   VAZQUEZ, LOUIS       On     03/02/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012302 Licensee Name: MAYER WEBER
Firm: 004699 Firm Name: COUNTY ELECL CONTRACTOR I
Firm Phone: 718-964-6090  Firm Address: 207 VAN BRUNT STREET BROOKLYN NY 11231 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
7 - HVAC WIRING
Total Fee:  $950.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: MICHAEL LEAVY
Owner Business Name: BAYLEY SETON HOSPITAL
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  3  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  11  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
006  150    190    75  275  10         
Buildings Total   190    75  275     10           
Total Units : 550 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: C - CALL TO OFFICE 02/14/2018
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: R153713
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/05/2018 02/06/2018 JTE V (60) (2)
INSPECTION COMMENTS: INSPECTION FAIL, NEED TO INSPECT RAISERS IN BSMT AN ALL HVAC SYSTEM, SEE OBJECTION DETAILS
 
(2) 02/12/2018 02/14/2018 OSZ V X (58) (5)
INSPECTION COMMENTS: CORRECT OBJECTIONS.
 
(3) 03/02/2018 03/02/2018 LV1 C R (100) (0)
INSPECTION COMMENTS: PASS

OBJECTION FOR APPLICATION #: R153713
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (143) LUMINAIRES NOT PROPERLY SUPPORTED/SECURED
(FLOOR: 006)ALL THROUGHOUT FIXTURES NOT PROPERLY SUPPORTED TO DROP CEILING
RSLV 02/05/2018 02/05/2018 03/02/2018
 
002 (228) USING PANEL AS A RACEWAY
(FLOOR: 006) PANELS THROUGHOUT
RSLV 02/05/2018 02/05/2018 03/02/2018
 
003 (999) OTHER
(FLOOR: 006)SETBACK IN ALL RECEPTACLES INSTALLED ON WOODEN CABINETS. ART 314.20
RSLV 02/12/2018 02/12/2018 03/02/2018
 
004 (999) OTHER
(ALL FLOORS)BONDING HAS NOT BEEN PROVIDED FOR ALL 480V PANELS/DISCO'S. ART.250.97
RSLV 02/12/2018 02/12/2018 03/02/2018
 
005 (123) SERVICE DISCONNECTS ARE NOT PROPERLY GROUPED/LABELED
(BASEMENT)480V 400 AMP DISCONNECT IN FIRST ELECTRICAL ROOM NOT PROPERLYLABELED. ART. 230.72(A/ART. 230.70(B))
RSLV 02/12/2018 02/12/2018 03/02/2018
 
006 (999) OTHER
(BASEMENT)CONDUITS GOING THOUGHT WALL FROM REAR ELECTRIC ROOM TO TROFF INHALLWAY HAVE NOT BEEN FIRE STOP/FIRE BLOCK. ART 300.21
RSLV 02/12/2018 02/12/2018 03/02/2018
 
007 (999) OTHER
(ROOF) AC UNITS ARE NOT PROPERLY LABELED. ART. 110.22(A)
RSLV 02/12/2018 02/12/2018 03/02/2018



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order