| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
3 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
11 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(143) |
LUMINAIRES NOT PROPERLY SUPPORTED/SECURED (FLOOR: 006)ALL THROUGHOUT FIXTURES NOT PROPERLY SUPPORTED TO DROP CEILING |
RSLV |
02/05/2018 |
02/05/2018 |
03/02/2018 |
| |
| 002 |
(228) |
USING PANEL AS A RACEWAY (FLOOR: 006) PANELS THROUGHOUT |
RSLV |
02/05/2018 |
02/05/2018 |
03/02/2018 |
| |
| 003 |
(999) |
OTHER (FLOOR: 006)SETBACK IN ALL RECEPTACLES INSTALLED ON WOODEN CABINETS. ART 314.20 |
RSLV |
02/12/2018 |
02/12/2018 |
03/02/2018 |
| |
| 004 |
(999) |
OTHER (ALL FLOORS)BONDING HAS NOT BEEN PROVIDED FOR ALL 480V PANELS/DISCO'S. ART.250.97 |
RSLV |
02/12/2018 |
02/12/2018 |
03/02/2018 |
| |
| 005 |
(123) |
SERVICE DISCONNECTS ARE NOT PROPERLY GROUPED/LABELED (BASEMENT)480V 400 AMP DISCONNECT IN FIRST ELECTRICAL ROOM NOT PROPERLYLABELED. ART. 230.72(A/ART. 230.70(B)) |
RSLV |
02/12/2018 |
02/12/2018 |
03/02/2018 |
| |
| 006 |
(999) |
OTHER (BASEMENT)CONDUITS GOING THOUGHT WALL FROM REAR ELECTRIC ROOM TO TROFF INHALLWAY HAVE NOT BEEN FIRE STOP/FIRE BLOCK. ART 300.21 |
RSLV |
02/12/2018 |
02/12/2018 |
03/02/2018 |
| |
| 007 |
(999) |
OTHER (ROOF) AC UNITS ARE NOT PROPERLY LABELED. ART. 110.22(A) |
RSLV |
02/12/2018 |
02/12/2018 |
03/02/2018 |