Electrical Application Details for App #: R148671
Premises: 3 NAVY PIER COURT STATEN ISLAND BIN: 5158986     Block: 487   Lot: 20
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 7 NAVY PIER COURT Census Tract:   21
ROOF AND CELLAR Admin Area:   R - STATEN ISLAND Inspection Area:   A
STATEN IS, NY 10304 Community Board:   501
Related Job Number:    520132963
DOB Cross Street(s):   FRONT STREET,    DEAD END
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   06/16/2016 Job Start Date:   06/07/2016
Last Change:   10/20/2025 Job End Date:   06/07/2017
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   VINCENT CASTALDO       On     04/11/2017      
Field Disp:   V - OBJCTN ISSD: JOB INCOMPLT
Energize Recommendation:  
Objection Disposition:  X - NOT REMOVED

License #: 012022 Licensee Name: JOSEPH SORTINO
Firm: 003742 Firm Name: TOP SHELF ELECTRIC CORP
Firm Phone: 718-815-1700  Firm Address: 3917 AMBOY ROAD STATEN ISLAND NY 10308 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $3,226.75
Hurricane Sandy Damage:   No
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Commercial/Residential (2  Stores, 571 Apartments)
Special Cert Approval:  
Advisory Board Approval:   REQUIRED
Advisory Board Categories:      K - 1000 KVA SERVICE                            
Advisory Board Approval #:   53845     Submittal #: 15A0393  
Owner / Occup: GEORGE RUSSO
Owner Business Name: HOMEPORT 1 LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  1  30A
B. 101 Up to 200 AMPS  1  200A
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  2  1-1200A, 1-4000A
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  #2
B. Over #2 to 1/0  13  2-#4,4-#6,7-#10
C. Over 1/0 to 250 MCM  10  #4/0
D. Over 250 MCM  18  13-600,3-500,2-350MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  2  1-4000A,1-250A
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL              35         
ROF              150         
Buildings Total              185           
Total Units : 185 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 9 #10-Wire 1
Existing Meters 0 + New Meters 10 - Removed Meters 0 = Total Meters 10

Power Auth Flag: I - ISSUED Objection Flag: V - OBJECTION(S) EXIST
Power Requested: 06/16/2016 Notice: C - CALL TO OFFICE 04/11/2017
Power Issued: 06/16/2016 Response:  

Follow-Up:
Contractor's Comments:  SERVICE WORK W/ADVISORY BOARD APPROVAL

 
Inspection Details
 

INSPECTION FOR APPLICATION #: R148671
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/06/2016 07/07/2016 JTE V (30) (1)
INSPECTION COMMENTS: ADVISORY BOARD DRAWINGS ARE NOT PER WORK SCOPE ALSO SAME CALENDAR NUMBER IS FOR TWO SEPARATE BUILDINGS BUT ONLY ONE APPLICATION ON FILE FOR THIS ADDRESS 7 NAVY PIER COURT BUT NO APPLICATION ON FILE FOR 8 NAVY PIER COURT, DRAWINGS MUST BE REVISE, NOT A FINAL INSPECTION.
 
(2) 01/11/2017 01/11/2017 FRI J X (5) (0) Y
INSPECTION COMMENTS: NEED REVISED ADVISORY DRAWINGS
 
(3) 04/11/2017 04/11/2017 VTC V X (186) (6)
INSPECTION COMMENTS: FAIL- NEED MORE TIME TO COMPLETE INSPECTION

OBJECTION FOR APPLICATION #: R148671
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 4) SERVICE IN EXCESS OF 1000KVA HAS NOT BEEN SUBMITTED FOR APPROVAL
(FLOOR: 002)ADVISORY BOARD DRAWINGS ARE NOT PER WORK SCOPE, MUST REVISE ANDAMEND LAY OUT OF ELECTRICAL ROOM, SERVICE SWITCHES, FEEDERS , PANELSAND TRANSFORMERS.
OPEN 07/06/2016 07/06/2016
 
002 (999) OTHER
(FLOOR: 002) ELECTRIC ROOM USED FOR STORAGE 110.25 NYC
OPEN 04/11/2017 04/11/2017
 
003 (999) OTHER
(FLOOR: 002) PENETRATIONS NOT SEALED UNDER SERVICE SWITCH 300.21
OPEN 04/11/2017 04/11/2017
 
004 (999) OTHER
(FLOOR: 002)CONDUITS NOT ENCASED IN CONCRETE AS PER ADVISORY BOARD DRAWING 110.3
OPEN 04/11/2017 04/11/2017
 
005 (999) OTHER
(FLOOR: 002) BONDING WIRE OF IMPROPER SIZE IN SERVICES SW'S 250.66
OPEN 04/11/2017 04/11/2017
 
006 (999) OTHER
(FLOOR: 002)ARC FAULT HAZARD LABELS AND 277/480 LABELS NOT PROVIDED 110.16
OPEN 04/11/2017 04/11/2017
 
007 (999) OTHER
(FLOOR: 002)SWITCH FOR TRANSFORMER IN MAIN ELECTRIC RM. NOT PROPERLY RATED 110.2NYC
OPEN 04/11/2017 04/11/2017