BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: R147235
Premises: 285 ST MARKS PLACE STATEN ISLAND BIN: 5000078     Block: 8   Lot: 25
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 285 ST. MARKS PL Census Tract:   3 Health Area:  0500
GROUND FLOOR Admin Area:   R - STATEN ISLAND Inspection Area:   A
STATEN IS, NY 10301 Community Board:   501
DOB Cross Street(s):   WALL STREET,    FORT PLACE
Status:   C - JOB IS SIGNED OFF 05/14/2022
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  02/10/2016 4:50 PM
Application Entered:   02/10/2016 Job Start Date:   02/12/2016
Last Change:   05/14/2022 Job End Date:   10/25/2016
Appointment Status:   
Last Inspection By:   ROBINSON HEATH       On     05/11/2022      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012729 Licensee Name: HARALABOS VASSOS
Firm: 002487 Firm Name: INFINITY ELEC'L CONTR'S I
Firm Phone: 917-299-6708  Firm Address: 22-10A 35TH STREET ASTORIA NY 11105 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $785.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: ROBERT FITZSIMMONS
Owner Business Name: GATEWAY ARMS REALTY C
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  1  200A
C. 201 Up to 600 AMPS  3  2 600A 1 400A
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  4  500 MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  2  42 C
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 92 #4-Wire 3 #10-Wire 0
Existing Meters 95 + New Meters 1 - Removed Meters 1 = Total Meters 95

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 02/10/2016 Notice: 1 - FIRST NOTICE 04/11/2022
Power Issued: 02/10/2016 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  REPLACING WATER DAMAGED S.S. EQUIPMENT AND WIRES

 
Inspection Details
 

INSPECTION FOR APPLICATION #: R147235
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 04/11/2022 04/11/2022 JTE V (40) (2)
INSPECTION COMMENTS: COMPLETE INSPECTION FAILED, SEE OBJECTION DETAILS
 
(2) 05/11/2022 05/11/2022 HRB C R (30) (0)
INSPECTION COMMENTS: INSPECTION COMPLETED NO OBJECTIONS ALL OBJECTIONS WERE REMOVED ON ANOTHER APP REFF# S00726144I1EL

OBJECTION FOR APPLICATION #: R147235
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
(BASEMENT) WATER MAIN G.E.C MISSING ( ART 250 ) 3/0 REQUIRED
RSLV 04/11/2022 04/11/2022 05/11/2022
 
002 (999) OTHER
(BASEMENT)FILE PAA TO ONLY ADD (1) 1600 AMP SERVICE SWITCH ABD DELETE OTHERSAND ALSO ADD (1) SET OF 3/0 FEEDERS.
RSLV 04/11/2022 04/11/2022 05/11/2022



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.