Electrical Application Details for App #: R146315
Premises: 75 VANDERBILT AVENUE STATEN ISLAND BIN: 5106863     Block: 534   Lot: 1
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 75 VANDERBILT AV Census Tract:   27 Health Area:  0500
7TH FLOOR Admin Area:   R - STATEN ISLAND Inspection Area:   A
STATEN IS, NY 10304 Community Board:   501
DOB Cross Street(s):   ERRINGTON PLACE,    TALBOT PLACE
Status:   C - JOB IS SIGNED OFF 08/25/2016
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  11/10/2015 11:04 PM
Application Entered:   11/10/2015 Job Start Date:   11/10/2015
Last Change:   08/25/2016 Job End Date:   11/09/2016
Appointment Status:   
Last Inspection By:   VINCENT CASTALDO       On     08/05/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012302 Licensee Name: MAYER WEBER
Firm: 004699 Firm Name: COUNTY ELECL CONTRACTOR I
Firm Phone: 718-964-6090  Firm Address: 207 VAN BRUNT STREET BROOKLYN NY 11231 

Historical Licensees and Firms:
License # Licensee Name Firm # Firm Name  
012302 WEBER, MAYER 004070 METRO ELEC'L CONTRS, INC

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
7 - HVAC WIRING
Total Fee:  $537.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   I - Hospital Or Health Facility
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: MICHAEL LEAVY
Owner Business Name: BAYLEY SETON HOSPITAL
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  3  
D. Over 250 MCM  0  
SUB FEEDERS (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  1  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  3  3X 4 #1 WIRE
D. 3 Phase Over 225 AMPS  1  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
007    100  70    45  100  10  20      45 
Buildings Total 100  70    45  100     20          45 
Total Units : 380 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 07/28/2016
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: R146315
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/27/2016 07/28/2016 VTC V (126) (4)
INSPECTION COMMENTS: FAIL
 
(2) 08/05/2016 08/05/2016 VTC C R (45) (0)
INSPECTION COMMENTS: PASS

OBJECTION FOR APPLICATION #: R146315
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (313) SIGNAGE NOT PROVIDED FOR ELECTRICAL CLOSET
(FLOOR: 007) SIGNAGE NEEDED FOR TWO CLOSETS
RSLV 07/27/2016 07/27/2016 08/05/2016
 
002 ( 53) GFCI HAS NOT BEEN PROVIDED
(FLOOR: 007) GFCI NOT PROVIDED IN JANITORS CLOSET
RSLV 07/27/2016 07/27/2016 08/05/2016
 
003 (999) OTHER
(FLOOR: 007) ARC FAULT HAZARD LABELS NEEDED FOR ALL PANELS 110.16
RSLV 07/27/2016 07/27/2016 08/05/2016
 
004 (999) OTHER
(FLOOR: 007) 277/480 LABEL NEEDED FOR PANEL 210.5
RSLV 07/27/2016 07/27/2016 08/05/2016