NYC Department of Buildings
Electrical Application Details for App #: R127037
Premises: 280 PARK HILL AVENUE STATEN ISLAND BIN: 5106239     Block: 2922   Lot: 1
  Printable (PDF) version of this Permit  

Filed: 280 PARK HILL AV Census Tract:   4000 Health Area:  0700
SOBEL COURT AND PALMA DRIVE Admin Area:   R - STATEN ISLAND Inspection Area:   A
STATEN IS, NY 10304 Community Board:   501
DOB Cross Street(s):   SOBEL COURT,    PALMA DRIVE
Status:   P - OBJECTN PENDING AT CONTRACTOR 07/01/2013
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  09/03/2010 2:27 PM
Application Entered:   09/03/2010 Job Start Date:   10/01/2010
Last Change:   07/01/2013 Job End Date:   12/31/2010
Appointment Status:   
Last Inspection By:   TREJO, JORGE       On     06/27/2013      
Field Disp:   A - OBJCTN ISSD: JOB COMPLETE
Energize Recommendation:  
Objection Disposition:  

License #: 010118 Licensee Name: ROBERT MARCHISOTTO
Firm: 002914 Firm Name: R.C.M. ELECTRIC CORP.
Firm Phone: 718-339-2680  Firm Address: 1915 MCDONALD AVE. BLDG REAR BROOKLYN NY 11223 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
Total Fee:  $290.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   L - Five Or More Family
Special Cert Approval:   L - FIRE ALARM LOCAL LAW #5
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: MARC WATKINS
Owner Business Name: KISMO APARTMENTS LLC
Authorized Representative:  MARC WATKINS
Relationship To Owner:   MANAGING AGENT


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  2  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 07/01/2013
Power Issued: Response:  

Follow-Up:
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: R127037
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/27/2013 07/01/2013 JTE A (60) (11) Y
INSPECTION COMMENTS: ELEVATOR NYC ID # 5P327/5P326

OBJECTION FOR APPLICATION #: R127037
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 53) GFCI HAS NOT BEEN PROVIDED
5P327/26 #14AWG INUSE TO FEED ELEV LIGHTING EQUIPMENT DISC/SW
OPEN 06/27/2013 06/27/2013
 
002 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
5P327/26 2 GROUND WIRES UNDER ONE LUG CONTROL CABINET
OPEN 06/27/2013 06/27/2013
 
003 (302) ELEVATOR MOTORS/CONTROLLERS/ENCLOSURES NOT GROUNDED
5P327/26 ELEV MOTOR DISC/SW NOT PROPERLY GROUNDED MISSING BONDINGSCREW OR LUG
OPEN 06/27/2013 06/27/2013
 
004 (192) CONDUCTORS ARE OVER FUSED AS PER TABLE 310.16
5P327/26 #14AWG CONDUCTORS BEING FUSED AT 100A
OPEN 06/27/2013 06/27/2013
 
005 ( 42) BUSHINGS ARE MISSING OR LOOSE
5P327/26 ELEV MOTOR DISC/SW MISSING 11/4" PLASTIC BUSHING
OPEN 06/27/2013 06/27/2013
 
006 (999) OTHER
5P326 2 NEUTRALS UNDER ONE SCREW LIGHTING DISC/SW 110.14
OPEN 06/27/2013 06/27/2013
 
007 ( 18) DEFECTIVE RECEPTACLES ARE IN USE
5P326 ELEV TOP GFCI DON'T RESIST
OPEN 06/27/2013 06/27/2013
 
008 ( 29) OUTLET BOXES ARE NOT COVERED
5P326 ELEV PIT SINGLE RECPTACLE MISSING PLATE COVER
OPEN 06/27/2013 06/27/2013
 
009 (999) OTHER
5P326 NO GFCI PROVIDED FOR ELEV PIT 620.24C
OPEN 06/27/2013 06/27/2013
 
010 (999) OTHER
5P326 NO SIGNLE RECEPTACLE PROVIDED ELEV PIT PUMP 620.25
OPEN 06/27/2013 06/27/2013
 
011 ( 45) FIXTURE NOT INSTALLED IN AN APPROVED MANNER
5P327/26 NO CAGE LIGHT FIXTURE PROVIDED FOR ELEVATOR PIT
OPEN 06/27/2013 06/27/2013