| BUILDING OVERVIEW |
Are Feeders Being Installed? : |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 3) |
APPLICATION FOR CERTIFICATE OF ELECTRICAL INSPECTION NOT ON FILE LIGHT, OUTLETS, SWITCHES, SERVICE WORK |
OPEN |
09/01/2009 |
09/01/2009 |
|
| |
| 002 |
( 1) |
SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER NONE OF THE SERVICE SWITCHES ARE BONDED |
OPEN |
09/01/2009 |
09/01/2009 |
|
| |
| 003 |
( 5) |
SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY MAIN GROUND WIRE NOT AT WATERMAIN |
OPEN |
09/01/2009 |
09/01/2009 |
|
| |
| 004 |
( 8) |
CONDUIT IS NOT PROPERLY SUPPORTED (TYPE:IMC) OUTSIDE SERVICE RACEWAY |
OPEN |
09/01/2009 |
09/01/2009 |
|
| |
| 005 |
( 10) |
BRANCH CIRCUIT CONDUCTORS ARE NOT PROPER SIZE IN AND BY MAIN SERVICE SWITCHES |
OPEN |
09/01/2009 |
09/01/2009 |
|
| |
| 006 |
( 11) |
FEEDER CONDUCTORS ARE NOT OF PROPER SIZE USING #12 WIRE TO FEED 100 AMP BRAKERS IN MAIN SERVICE SWITCHES |
OPEN |
09/01/2009 |
09/01/2009 |
|
| |
| 007 |
( 15) |
FLEXIBLE CORDS USED AS PERMANENT WIRING METHOD THROUGHOUT |
OPEN |
09/01/2009 |
09/01/2009 |
|
| |
| 008 |
( 16) |
DEFECTIVE LIGHTING FIXTURES ARE IN USE THROUGHOUT |
OPEN |
09/01/2009 |
09/01/2009 |
|
| |
| 009 |
( 17) |
DEFECTIVE SWITCHES ARE IN USE THROUGHOUT |
OPEN |
09/01/2009 |
09/01/2009 |
|
| |
| 010 |
( 19) |
DEFECTIVE WIRING IS IN USE THROUGHOUT AND BY MAIN SERVICE SWITCHES |
OPEN |
09/01/2009 |
09/01/2009 |
|
| |
| 011 |
( 56) |
ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED USING #12 WIRE TO FEED OTHER SERVICE SWITCHES, PANEL INSTALLED INCLOSET IN BASEMENT |
OPEN |
09/01/2009 |
09/01/2009 |
|
| |
| 012 |
( 62) |
ELECTRICAL PERMIT IS NOT CONSPICUOUSLY POSTED AT THE SITE
|
OPEN |
09/01/2009 |
09/01/2009 |
|
| |
| 013 |
(999) |
OTHER SERVICE MAST ISNOT SUPPORTED PROPERLY (230-28) |
OPEN |
09/01/2009 |
09/01/2009 |
|
| |
| 014 |
(999) |
OTHER PANEL IS INSTALLED IN CLOSET IN BASEMENT (240.24D) |
OPEN |
09/01/2009 |
09/01/2009 |
|
| |
| 015 |
(999) |
OTHER SERVICE LOOP IS NOT ATTACHED TO THE HOUSE (230.27) |
OPEN |
09/01/2009 |
09/01/2009 |
|
| |
| 016 |
(999) |
OTHER NO GFI PROTECTION FOR NEW OUTLETS ON KITCHEN COUNTER (210.52) |
OPEN |
09/01/2009 |
09/01/2009 |
|
| |
| 017 |
( 33) |
KNOCKOUTS ARE NOT CLOSED IN OUTLET BOX THROUGHOUT HOUSE |
OPEN |
09/01/2009 |
09/01/2009 |
|
| |
| 018 |
( 34) |
KNOCKOUTS ARE NOT CLOSED IN PANEL BOX IN MAIN SERVICE SWITCHES, COVERS MISSING |
OPEN |
09/01/2009 |
09/01/2009 |
|