Electrical Application Details for App #: R124549
Premises: 80 BROAD STREET STATEN ISLAND BIN: 5013834     Block: 529   Lot: 7
   

DOB NOW: Inspections


Filed: 80 BROAD ST Census Tract:   27 Health Area:  0500
THROUGHOUT Admin Area:   R - STATEN ISLAND Inspection Area:   A
STATEN IS, NY 10304 Community Board:   501
DOB Cross Street(s):   WRIGHT STREET,    QUINN STREET
Status:   E - ABANDONED 08/22/2025
Request Type:   P - PICK-UP eFiled:   NO
Application Entered:   09/03/2009 Job Start Date:  
Last Change:   08/22/2025 Job End Date:  
Appointment Status:   
Last Inspection By:   ROBINSON HEATH       On     09/01/2009      
Field Disp:   W - ISSUE OBJECTION TO OWNER
Energize Recommendation:  
Objection Disposition:  

License #: Licensee Name: UNKNOWN
Firm: Firm Name: UNKNOWN
Firm Phone:   Firm Address:  

Work Started or Filed by Others: NO
Work Category:    Work To Be Done:   Total Fee:  $0.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   A - One Family
Special Cert Approval:  
Advisory Board Approval:  
Owner / Occup: TONY LAMORTE
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 09/03/2009
Power Issued: Response:  

Follow-Up: V - OWNER OBJECTION 09/03/2009
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: R124549
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 09/01/2009 09/03/2009 HRB W (70) (18)
INSPECTION COMMENTS: HAZERDOUS LOCATION; NOT FINAL; NEED TO RECHECK EVERYTHING, NO ACCESS TO ATTIC APARTMENT

OBJECTION FOR APPLICATION #: R124549
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 3) APPLICATION FOR CERTIFICATE OF ELECTRICAL INSPECTION NOT ON FILE
LIGHT, OUTLETS, SWITCHES, SERVICE WORK
OPEN 09/01/2009 09/01/2009
 
002 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
NONE OF THE SERVICE SWITCHES ARE BONDED
OPEN 09/01/2009 09/01/2009
 
003 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
MAIN GROUND WIRE NOT AT WATERMAIN
OPEN 09/01/2009 09/01/2009
 
004 ( 8) CONDUIT IS NOT PROPERLY SUPPORTED (TYPE:IMC)
OUTSIDE SERVICE RACEWAY
OPEN 09/01/2009 09/01/2009
 
005 ( 10) BRANCH CIRCUIT CONDUCTORS ARE NOT PROPER SIZE
IN AND BY MAIN SERVICE SWITCHES
OPEN 09/01/2009 09/01/2009
 
006 ( 11) FEEDER CONDUCTORS ARE NOT OF PROPER SIZE
USING #12 WIRE TO FEED 100 AMP BRAKERS IN MAIN SERVICE SWITCHES
OPEN 09/01/2009 09/01/2009
 
007 ( 15) FLEXIBLE CORDS USED AS PERMANENT WIRING METHOD
THROUGHOUT
OPEN 09/01/2009 09/01/2009
 
008 ( 16) DEFECTIVE LIGHTING FIXTURES ARE IN USE
THROUGHOUT
OPEN 09/01/2009 09/01/2009
 
009 ( 17) DEFECTIVE SWITCHES ARE IN USE
THROUGHOUT
OPEN 09/01/2009 09/01/2009
 
010 ( 19) DEFECTIVE WIRING IS IN USE
THROUGHOUT AND BY MAIN SERVICE SWITCHES
OPEN 09/01/2009 09/01/2009
 
011 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
USING #12 WIRE TO FEED OTHER SERVICE SWITCHES, PANEL INSTALLED INCLOSET IN BASEMENT
OPEN 09/01/2009 09/01/2009
 
012 ( 62) ELECTRICAL PERMIT IS NOT CONSPICUOUSLY POSTED AT THE SITE
OPEN 09/01/2009 09/01/2009
 
013 (999) OTHER
SERVICE MAST ISNOT SUPPORTED PROPERLY (230-28)
OPEN 09/01/2009 09/01/2009
 
014 (999) OTHER
PANEL IS INSTALLED IN CLOSET IN BASEMENT (240.24D)
OPEN 09/01/2009 09/01/2009
 
015 (999) OTHER
SERVICE LOOP IS NOT ATTACHED TO THE HOUSE (230.27)
OPEN 09/01/2009 09/01/2009
 
016 (999) OTHER
NO GFI PROTECTION FOR NEW OUTLETS ON KITCHEN COUNTER (210.52)
OPEN 09/01/2009 09/01/2009
 
017 ( 33) KNOCKOUTS ARE NOT CLOSED IN OUTLET BOX
THROUGHOUT HOUSE
OPEN 09/01/2009 09/01/2009
 
018 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
IN MAIN SERVICE SWITCHES, COVERS MISSING
OPEN 09/01/2009 09/01/2009