BIS Menu  |  Pre-BIS PA CO Query By Bin  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: R121439
Premises: 118 SCRIBNER AVENUE STATEN ISLAND BIN: 5000730     Block: 36   Lot: 22
   

DOB NOW: Inspections


Filed: 118 SCRIBNER AV Census Tract:   11 Health Area:  0400
BASEMENT AND 2ND FLOOR Admin Area:   R - STATEN ISLAND Inspection Area:   A
STATEN IS, NY 10301 Community Board:   501
DOB Cross Street(s):   BISMARK AVENUE,    BRIGHTON AVENUE
Status:   E - ABANDONED 08/22/2025
Request Type:   P - PICK-UP eFiled:   NO
Application Entered:   06/11/2008 Job Start Date:  
Last Change:   08/22/2025 Job End Date:  
Appointment Status:   
Last Inspection By:   PORAZZO, P       On     06/10/2008      
Field Disp:   W - ISSUE OBJECTION TO OWNER
Energize Recommendation:  
Objection Disposition:  

License #: Licensee Name: UNKNOWN
Firm: Firm Name: UNKNOWN
Firm Phone:   Firm Address:  

Work Started or Filed by Others: NO
Work Category:    Work To Be Done:   Total Fee:  $0.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   A - One Family
Special Cert Approval:  
Advisory Board Approval:  
Owner / Occup: DELE OLADAPO
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 06/11/2008
Power Issued: Response:  

Follow-Up: V - OWNER OBJECTION 06/11/2008
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: R121439
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/10/2008 06/11/2008 PP1 W (20) (11)
INSPECTION COMMENTS: X

OBJECTION FOR APPLICATION #: R121439
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
SERVICE SWITCH NOT BONDED BASEMENT
OPEN 06/10/2008 06/10/2008
 
002 ( 3) APPLICATION FOR CERTIFICATE OF ELECTRICAL INSPECTION NOT ON FILE
FOR CHANGING OF SERVICE SWITCH, FEEDERS, FIXTURES, RECS & SWITCHES(BASEMENT & 2ND FLOOR)
OPEN 06/10/2008 06/10/2008
 
003 ( 8) CONDUIT IS NOT PROPERLY SUPPORTED (TYPE:IMC)
OUTSIDE CONDUIT TOP OF SERVICE
OPEN 06/10/2008 06/10/2008
 
004 ( 24) ARMORED CABLES ARE NOT PROPERLY SECURED
BASEMENT
OPEN 06/10/2008 06/10/2008
 
005 ( 29) OUTLET BOXES ARE NOT COVERED
BASEMENT
OPEN 06/10/2008 06/10/2008
 
006 ( 30) OUTLET BOXES ARE NOT SECURED
BASEMENT
OPEN 06/10/2008 06/10/2008
 
007 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
BASEMENT
OPEN 06/10/2008 06/10/2008
 
008 ( 36) CONDUCTORS ARE NOT PROPERLY COLOR CODED
IN BASEMENT FOR 2ND FLOOR PANEL
OPEN 06/10/2008 06/10/2008
 
009 ( 42) BUSHINGS ARE MISSING OR LOOSE
M.I.G.B MISSING 2ND FLOOR PANEL IN BASEMENT
OPEN 06/10/2008 06/10/2008
 
010 (999) OTHER
SERVICE SWITCH INSTALLED NO MAIN BREAKER (230.70)
OPEN 06/10/2008 06/10/2008
 
011 (999) OTHER
SPLICE BOXES BURRIED BASEMENT BY STAIRS
OPEN 06/10/2008 06/10/2008



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Pre-BIS PA CO Query By Bin  |  Electrical Inspection Work Order  |  Back