Premises: 56 LEONARD STREET MANHATTAN BIN: 1088646     Block: 176   Lot: 7501
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 56 LEONARD ST Census Tract:   33
ENTIRE BUILDING C-58 Admin Area:   M - MANHATTAN Inspection Area:   W
NEW YORK, NY 10013 Community Board:   101
Related Job Number:    104799648
DOB Cross Street(s):   WEST BROADWAY,    CHURCH STREET
Status:   C - JOB IS SIGNED OFF 05/10/2018
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   12/08/2017 Job Start Date:   11/10/2017
Last Change:   05/10/2018 Job End Date:   11/10/2019
Appointment Status:   
Last Inspection By:   DIAMOND, R.       On     05/09/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011575 Licensee Name: DANIEL LIVINGSTON
Firm: 003096 Firm Name: LIVINGSTON ELEC'L ASSOC.
Firm Phone: 718-969-2700  Firm Address: 162-20 77TH ROAD (INC.) FLUSHING NY 11366 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
7 - HVAC WIRING
8 - BOILER/BURNER WIRING
L - LIGHTING WORK
Total Fee:  $5,040.00
Hurricane Sandy Damage:   No
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   Yes
Job Number:  104799648
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   REQUIRED
Advisory Board Categories:      K - 1000 KVA SERVICE                            
Advisory Board Approval #:   54726     Submittal #: 12A0262  
Owner / Occup: KEYVAN KAZEMI
Owner Business Name: 56 LEONARD LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  2  2-60A
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  6  4-600A,2-400A
D. 601 Up to 1200 AMPS  4  2-800A,2-1200A
E. Over 1200 AMPS  5  1-3000A,3-2500A,1-1600A
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  22  22-VARIES
B. Over #2 to 1/0  22  22-VARIES
C. Over 1/0 to 250 MCM  147  147-VARIES
D. Over 250 MCM  154  154-VARIES
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  136  136@45-1
C. 3 Phase Up to 225 AMPS  38  24-100A,14-225A
D. 3 Phase Over 225 AMPS  21  21-VARIES
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL    50  25    15  50  23  200      500 
LOB    50  25    10  50  11  100         
002    50  25    15  50  20  11  110  150 
003    50  15  10  50            2140 
004    50  25    17  50  11  90         
005    55  25    18  55  10      150 
006    60  30    20  60  16  370  20     
007    40  20    10  40  12  20         
008    100  145    50  100      62  27     
009    100  145    118  100      62  27     
010    100  145    118  100      62  27     
011    100  145    118  100      62  27     
012    100  145    118  100      62  27     
013    100  145    118  100      62  27     
014    100  145    118  100      62  27     
015    100  145    118  100      62  27     
016    100  145    118  100      62  27     
017    100  145    118  100      62  27     
018    100  145    118  100      62  27     
019    100  145    118  100      62  27     
020    100  145    118  100      62  27     
021    100  145    118  100      62  27     
022    100  145    118  100      62  27     
023    100  145    118  100      62  27     
024    100  145    118  100      62  27     
025    100  145    118  100      62  27     
026    100  145    118  100      62  27     
027    100  145    118  100      62  27     
028    100  145    118  100      62  27     
029    100  145    118  100      62  27     
030    100  145    118  100      62  27     
031    100  145    118  100      62  27     
032    50  10    15  50  25  215      120 
033    90  130    106  90      56  25  45 
034    90  130    106  90      56  25     
035    90  130    106  90      56  25     
036    90  130    106  90      56  25     
037    90  130    106  90      56  25     
038    90  130    106  90      56  25     
039    90  130    106  90      56  25     
040    90  130    106  90      56  25     
041    90  130    106  90      56  25     
042    90  130    106  90      56  25     
043    90  130    106  90      56  25     
044    90  130    106  90      56  25     
045    90  130    106  90      56  25     
046    50  25    15  50  12  15      30 
047    80  117    95  50      50  20     
048    80  117    95  50      50  20     
049    80  117    95  50      50  20     
050    80  117    95  50      50  20     
051    80  117    95  50      50  20     
052    80  117    95  50      50  20     
053    80  117    95  50      50  20     
054    80  117    95  50      50  20     
055    80  117    95  50      50  20     
056    50  25    17  50  17  290      150 
057    10    10  59      45 
058                  50     
Buildings Total 4855  6478  10  5204  4535     1389     1333     3330 
Total Units : 27134 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 1 #10-Wire 4
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 12/08/2017 Notice: 1 - FIRST NOTICE 02/27/2018
Power Issued: 12/08/2017 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  PERMANENT LIGHT & POWER (TO REPLACE ONLINE APP M340650)

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M405015
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/22/2018 02/27/2018 RDI V (225) (8)
INSPECTION COMMENTS: REINSPECT REQUIRED WITH REVISED PLAN. APPLICATION WORK AMENDMENTS REQUIRED PRIOR TO APOINT. GEN FRAME GROUND TO BE IDENTIFIED.
 
(2) 05/09/2018 05/10/2018 RDI C R (70) (0)
INSPECTION COMMENTS: CAL# 54726 REVISED

OBJECTION FOR APPLICATION #: M405015
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(ALL FLOORS)FIRE STOPS NOT PROVIDED FOR CONDUITS BETWEEN CINDER BLOCK WALLSWHERE OBSERVED. (300.21).
RSLV 02/22/2018 02/22/2018 05/09/2018
 
002 ( 4) SERVICE IN EXCESS OF 1000KVA HAS NOT BEEN SUBMITTED FOR APPROVAL
(BASEMENT)NEW REVISION REQUIRED AT TIME O F INSPECTION. (REINSPECT REQUIRED).
RSLV 02/22/2018 02/22/2018 05/09/2018
 
003 (999) OTHER
(BASEMENT) 277/480 ROOF PUMP RACEWAY NOT BONDED. (SERV RM)
RSLV 02/22/2018 02/22/2018 05/09/2018
 
004 (999) OTHER
(BASEMENT)110V ROOF PUMP S/S NEUTRAL NOT PROPERLY BONDED TO ENCLOSURE ASDESIGNED. (SERV RM).
RSLV 02/22/2018 02/22/2018 05/09/2018
 
005 (999) OTHER
(CELLAR) 277/480 FP RIGID FEEDER NOT BONDED, NO BUSHING.
RSLV 02/22/2018 02/22/2018 05/09/2018
 
006 ( 19) DEFECTIVE WIRING IS IN USE
(PENTHOUSE) NEUTRAL CONDUCTOR ATTACHED ON GROUND BUSS IN PNL.
RSLV 02/22/2018 02/22/2018 05/09/2018
 
007 ( 25) ARMORED CABLES ARE NOT PROPERLY TERMINATED
(PENTHOUSE) BX IMPROPERLY TERMINATED IN APART. PNL.
RSLV 02/22/2018 02/22/2018 05/09/2018
 
008 ( 27) ARMORED CABLES INSTALLED WITHOUT INSULATING BUSHINGS
(PENTHOUSE) ARMOR CABLE MISSING BUSHINGS.
RSLV 02/22/2018 02/22/2018 05/09/2018