BIS Menu  |  Applications  |  Plumb. Inspections  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M404962
Premises: 20 HUDSON YARDS MANHATTAN BIN: 1088961     Block: 702   Lot: 7501
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 500 W 33 ST Census Tract:   99
38TH FLOOR Admin Area:   M - MANHATTAN Inspection Area:   Q
NEW YORK, NY 10001 Community Board:   104
Special Place Name:   HBO
DOB Cross Street(s):    10 AVENUE,    HUDSON BOULEVARD EAST
Status:   C - JOB IS SIGNED OFF 07/16/2019
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   12/06/2017 Job Start Date:   11/20/2017
Last Change:   07/16/2019 Job End Date:   11/20/2018
Appointment Status:   
Last Inspection By:   RIVERA, F       On     04/19/2019      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012869 Licensee Name: ELTON ZYKA
Firm: 004206 Firm Name: ALLRAN ELECTRIC OF NY LLC
Firm Phone: 212-269-5700  Firm Address: 120 BROADWAY, 36TH FLOOR NEW YORK NY 10005 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $2,674.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: TW NY PROPERTIES LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  13  3#4, 4#2
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  6  4-250, 4#3/0
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  17  9-100A, 8-225A
D. 3 Phase Over 225 AMPS  8  2-600A,2-2400A,4-1200A
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
038    90  368    44  584          1800 
Buildings Total 90  368    44  584               1800 
Total Units : 2886 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 02/15/2019
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  N/A

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M404962
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/14/2019 02/15/2019 MJD V (230) (2)
INSPECTION COMMENTS: FAIL,
 
(2) 04/19/2019 04/19/2019 FRI J Y (0) (0)
INSPECTION COMMENTS: CERTIFIED - OBJ-19-000008076
 
(3) 04/19/2019 04/19/2019 FRI C R (0) (0)
INSPECTION COMMENTS: CERTIFIED - OBJ-19-000008078

OBJECTION FOR APPLICATION #: M404962
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(FLOOR: 038) PANEL MISSING COVER ART. 314.25
RSLV 02/14/2019 02/14/2019 04/19/2019
 
002 (999) OTHER
(FLOOR: 038)FEEDER UNDERSIZED, 2500 AMP BREAKER FEED WITH 5 SETS OF 600MCM TABLE310.15
RSLV 02/14/2019 02/14/2019 04/19/2019



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Applications  |  Plumb. Inspections  |  Electrical Inspection Work Order  |  Back