BIS Menu  |  Property Profile  |  ECB Violations  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M404792
Premises: 436 EAST 13 STREET MANHATTAN BIN: 1090881     Block: 440   Lot: 26
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 436 E13ST Census Tract:   34 Health Area:  6200
COMPLETE BLD Admin Area:   M - MANHATTAN Inspection Area:   T
NEW YORK, NY 10009 Community Board:   103
Related Job Number:    121192477
DOB Cross Street(s):    1 AVENUE,    AVENUE A
Status:   C - JOB IS SIGNED OFF 01/15/2021
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  11/30/2017 10:26 PM
Application Entered:   11/30/2017 Job Start Date:   12/01/2017
Last Change:   01/15/2021 Job End Date:   12/01/2019
Appointment Status:   
Last Inspection By:   SHERON MEYERS       On     12/06/2020      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010458 Licensee Name: JOSEPH A SKARULIS
Firm: 001594 Firm Name: JOSEPH SKARULIS
Firm Phone: 718-565-8282  Firm Address: 245 WILSON AVENUE BROOKLYN NY 11237 

Work Started or Filed by Others: YES
Work Category:   N - NEW BUILDING Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
L - LIGHTING WORK
T - TEMPORARY LIGHT & POWER
Total Fee:  $950.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   Yes
Job Number:  121192477
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: DAVID AMIRIAN
Owner Business Name: BRIGETON AMIRIAN 13TH ST
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  1  200AMP
C. 201 Up to 600 AMPS  2  400AMP
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  #3
B. Over #2 to 1/0  6  1/0
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  6  30CKT
C. 3 Phase Up to 225 AMPS  1  42CKT
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS    20  28    22  10  15         
SWL    20      18         
001    12  42    16  25         
002    46    17  28         
003    46    17  28         
004    46    17  28         
005    46    17  28         
006    46    17  28         
ROF    13  16  13  20         
Buildings Total 105  325  125  206     47         
Total Units : 812 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 6 #4-Wire 2 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 11/30/2017 Notice: 1 - FIRST NOTICE 08/17/2020
Power Issued: 11/30/2017 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  ALL ELECTRICAL EXCEPT ELEVATOR

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M404792
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 08/16/2020 08/17/2020 SWR V (60) (3)
INSPECTION COMMENTS: FAIL. INSPECTION COMPLETE. OBJECTION ISSUED. ( CONTRACTOR LND ELECTRICAL ) NEEDS TO FILE NEW APPLICATION TO CORRECT OBJECTIONS ON APP # M404792. AND INCLUDE DETAIL AND DESCRIPTION OF SCOPE OF WORK.
 
(2) 12/06/2020 12/06/2020 SWR C R (60) (0)
INSPECTION COMMENTS: PASS. INSPECTION COMPLETE. WITH APP NUMBER M00423250. ALL OBJECTIONS REMOVED.

OBJECTION FOR APPLICATION #: M404792
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (123) SERVICE DISCONNECTS ARE NOT PROPERLY GROUPED/LABELED
(BASEMENT) SERVICE SWITCHES NOT MARKED T-OUT. 230.72 (A)
RSLV 08/16/2020 08/16/2020 12/06/2020
 
002 (269) FIRE PUMP SUPPLY CONDUCTORS NOT PROPERLY INSTALLED
(BASEMENT) RIGID CONDUIT NOT PROVIDED FOR FIRE PUMP. AM 695.6
RSLV 08/16/2020 08/16/2020 12/06/2020
 
003 (272) EQUIPMENT GROUNDING CONDUCTOR NOT PROPERLY INSTALLED
(BASEMENT)NO ACCESS TO GROUND COLLECTOR BAR AND SUPPLEMENTAL GROUND. 250.52
RSLV 08/16/2020 08/16/2020 12/06/2020



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.