BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M404587
Premises: 150 WEST 10 STREET MANHATTAN BIN: 1010679     Block: 610   Lot: 42
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 181 WAVERLY PL Census Tract:   71 Health Area:  6100
BAS, 001, 002, 003, 004, 005 Admin Area:   M - MANHATTAN Inspection Area:   R
NEW YORK, NY 10014 Community Board:   102
DOB Cross Street(s):   CHRISTOPHER STREET,    WEST 10 STREET
Status:   C - JOB IS SIGNED OFF 05/17/2018
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  11/27/2017 1:21 PM
Application Entered:   11/27/2017 Job Start Date:   11/27/2017
Last Change:   05/17/2018 Job End Date:   11/16/2018
Appointment Status:   
Last Inspection By:   CONROY BLAKE       On     02/09/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012622 Licensee Name: YUDA J FURTH
Firm: 004457 Firm Name: CITY WIDE ELECL CONTS INC
Firm Phone: 718-506-2287  Firm Address: 338 FLUSHING AVENUE BROOKLYN NY 11205 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $49.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: ADVANCED ENERGY
Owner Business Name: RESOURCES
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS                     
001                     
002                     
003                     
004                     
005                     
Buildings Total 24        24                
Total Units : 48 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 01/25/2018
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  PLP & STAIRWELL

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M404587
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 12/12/2017 12/12/2017 EDB V (50) (2)
INSPECTION COMMENTS: SEE ATTACHMENT.
 
(2) 01/25/2018 01/25/2018 AYC V Y (60) (1)
INSPECTION COMMENTS: FAIL
 
(3) 02/09/2018 02/12/2018 CBK C R (40) (0)
INSPECTION COMMENTS: OBJECTIONS RESOLVED.

OBJECTION FOR APPLICATION #: M404587
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
(ALL FLOORS) LIGHT FIXTURES NOT PROPERLY GND250.112,118,122
RSLV 12/12/2017 12/12/2017 02/09/2018
 
002 ( 25) ARMORED CABLES ARE NOT PROPERLY TERMINATED
(ALL FLOORS)AC CABLE NOT PROPERLY TERMINATED 320.40
RSLV 12/12/2017 12/12/2017 01/25/2018
 
003 (999) OTHER
(ALL FLOORS)IMPROPER SCREWS INSTALLED FOR FIXTURE INSTALLATION THROUGHOUT. ART.250.8
RSLV 01/25/2018 01/25/2018 02/09/2018



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back