BIS Menu  |  Pre-BIS PA CO Query By Bin  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M404385
Premises: 338 WEST 36 STREET MANHATTAN BIN: 1090378     Block: 759   Lot: 61
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 338 W 36TH ST Census Tract:   111 Health Area:  5500
ENTIRE Admin Area:   M - MANHATTAN Inspection Area:   Q
NEW YORK, NY 10018 Community Board:   104
Related Job Number:    121192066
DOB Cross Street(s):    8 AVENUE,    9 AVENUE
Status:   C - JOB IS SIGNED OFF 04/15/2019
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  11/20/2017 11:03 AM
Application Entered:   11/20/2017 Job Start Date:   11/20/2017
Last Change:   04/15/2019 Job End Date:   11/20/2019
Appointment Status:   
Last Inspection By:   SCHULER, THOMAS       On     04/12/2019      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012127 Licensee Name: LUIGI MARCELLINO
Firm: 003832 Firm Name: PRINCE ELEC'L CONTR'G COR
Firm Phone: 718-792-7292  Firm Address: 1140 BRONX RIVER AVENUE BRONX NY 10472 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $5,040.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   H - Hotel
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: SAM CHANG
Owner Business Name: 338 WEST LLC
Authorized Representative:  PETER SERPICO
Relationship To Owner:   CONSTRUCTION MANAGER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  12  22-#2
B. Over #2 to 1/0  7  1/0
C. Over 1/0 to 250 MCM  20  3/0
D. Over 250 MCM  7  7-600
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  30  42CT
D. 3 Phase Over 225 AMPS  3  1-1600AMP, 1-400 AMP 60CT
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL    250  170    40  250  11  50         
GND    211  88    30  211  17  50         
002    88  172    80  88  20  20         
003    88  172    80  88  20  20         
004    88  172    80  88  20  20         
005    88  172    80  88  20  20         
006    88  172    80  88  20  20         
007    88  172    80  88  20  20         
008    88  172    80  88  20  20         
009    88  172    80  88  20  20         
010    88  172    80  88  20  20         
011    88  172    80  88  20  20         
012    88  172    80  88  20  20         
013    88  172    80  88  20  20         
014    88  172    80  88  20  20         
015    88  172    80  88  20  20         
016    88  172    80  88  20  20         
017    88  172    80  88  20  20         
018    88  172    80  88  20  20         
019    88  172    80  88  20  20         
020    88  172    80  88  20  20         
021    88  172    80  88  20  20         
022    88  172    80  88  20  20         
023    88  172    80  88  20  20         
024    88  172    80  88  20  20         
025    88  172    80  88  20  20         
026    88  172    80  88  20  20         
027    88  172    80  88  20  20         
028    88  172    80  88  20  20         
ROF    30    30  77  185  43     
Buildings Total 2867  4908    2235  2867     825     43      
Total Units : 13745 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 03/01/2019
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  N/A

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M404385
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/28/2019 03/01/2019 RDI V (165) (4)
INSPECTION COMMENTS: ALL ROOMS AND FLOORS INSPECTED.
 
(2) 03/07/2019 03/07/2019 FRI J Y (0) (0)
INSPECTION COMMENTS: CERTIFIED - OBJ-19-000004801
 
(3) 03/08/2019 03/08/2019 FRI J Y (0) (0)
INSPECTION COMMENTS: CERTIFIED - OBJ-19-000004799
 
(4) 03/08/2019 03/08/2019 TUR J Y (0) (0)
INSPECTION COMMENTS: CERTIFIED - OBJ-19-000004800
 
(5) 04/12/2019 04/12/2019 TUR C R (1) (0)
INSPECTION COMMENTS: OBJ . REMOVED AS PER RDI

OBJECTION FOR APPLICATION #: M404385
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (239) GFCI HAS NOT BEEN PROVIDED
(FLOOR: 001)COFFEE DISPENCERS DIRECT CONNECT TO WATER SYSTEM FOR PUBLIC USE.
RSLV 02/28/2019 02/28/2019 03/08/2019
 
002 (999) OTHER
(FLOOR: 001)PENDANT OUTLET BOXES COVERED BY WOOD SUSPENDED CEILING WITH NOACESS.
RSLV 02/28/2019 02/28/2019 03/08/2019
 
003 (999) OTHER
(ALL FLOORS)ROOMS NOT WIRIED IN COMPLIANCE OF ENERGY CODE (C405.2.4) NO MASTERCONTROL DEVICE INSTALLED ON LUMINAIRES AND SWITCHED RECEPTACLES.
RSLV 02/28/2019 02/28/2019 04/12/2019
 
004 (132) EQUIPMENT/MATERIAL IS NOT PROPERLY GROUNDED
(ROOF) GENERATOR FRAME GROUND NOT PROVIDED.
RSLV 02/28/2019 02/28/2019 03/07/2019



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.