BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M404329
Premises: 550 WEST 33 STREET MANHATTAN BIN: 1091590     Block: 702   Lot: 150
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 560 W 33RD ST Census Tract:   99 Health Area:  5500
35 HUDSON YARDS Admin Area:   M - MANHATTAN Inspection Area:   Q
NEW YORK, NY 10001 Community Board:   104
Special Place Name:   TOWER E
Related Job Number:    121192618
DOB Cross Street(s):   HUDSON BOULEVARD EAST,    11 AVENUE
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  11/17/2017 3:38 PM
Application Entered:   11/17/2017 Job Start Date:   11/17/2017
Last Change:   08/22/2025 Job End Date:   09/30/2019
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   SOLAVNTO, THOMAS       On     02/11/2021      
Field Disp:   J - JOB IN PROGRESS
Energize Recommendation:  
Objection Disposition:  Y - PARTLY REMOVED

License #: 010702 Licensee Name: AGNELLO DIVINCENZO
Firm: 001559 Firm Name: ZWICKER ELEC. CO., INC.
Firm Phone: 212-477-8400  Firm Address: 360 PARK AVE. SOUTH NEW YORK NY 10010 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
6 - GENERAL WIRING
L - LIGHTING WORK
Total Fee:  $5,040.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   Yes
Job Number:  121192618
Building Used As:   Z - Other
Store / Other:   MIXED USE
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: RONALD WACKROW
Owner Business Name: ERY NORTH TOWER RHC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  6  4#750KCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  38  400A
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001    137  38    140             
002    76  36      135             
003    250  25    200             
MZ3      25                   
004    24      24             
005    44  25    22             
007    200  30    200             
MZ7    25               
008    42  37      42             
009    42  37      42             
010    42  37      42             
011    42  37      42             
012    42  37      42             
013    42  37      42             
014    275  30    227             
M14    39  25    13             
017    129  190    369             
018    148  99    296  22         
019    148  99    296  22         
020    148  100    296  22         
021    148  100    296  22         
022    148  100    298  22         
023    149  100    298  22         
024    149  100    298  22         
025    149  100    299  22         
026    149  100    299  23         
027    149  100    299  23         
028    150  100    300  22         
029    150  100    300  22         
Buildings Total 3212  1869    63  5158     12           
Total Units : 10314 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 03/09/2020
Power Issued: Response:  

Follow-Up:
Contractor's Comments:  N/A

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M404329
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 08/17/2019 08/19/2019 VTC V (474) (3)
INSPECTION COMMENTS: FAIL - SEE LIST
 
(2) 03/07/2020 03/09/2020 MJD V R (360) (3)
INSPECTION COMMENTS: FAIL, OBJECTIONS ISSUED
 
(3) 03/11/2020 03/11/2020 FRI J Y (0) (0)
INSPECTION COMMENTS: CERTIFIED - OBJ-20-000007545
 
(4) 02/11/2021 02/11/2021 TSO J Y (0) (0)
INSPECTION COMMENTS: CERTIFIED - OBJ-21-000005064

OBJECTION FOR APPLICATION #: M404329
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(ALL FLOORS) HOTEL RECEPTACLES NOT PROPERLY GROUNDED 250.146
RSLV 08/17/2019 08/17/2019 03/07/2020
 
002 (999) OTHER
(ALL FLOORS)LIGHTING JUNCTION BOXES WHERE M/C CABLE IS BEING USED ARE NOTPROPERLY GROUNDED 250.148C
RSLV 08/17/2019 08/17/2019 03/07/2020
 
003 (999) OTHER
(ALL FLOORS)LIGHTING FIXTURES NOT PROPERLY SUPPORTED IN SUSPENDED CEILINGS410.36B
RSLV 08/17/2019 08/17/2019 03/07/2020
 
004 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(ALL FLOORS)ART. 110.3 20 AMP BREAKERS INSTALLED FOR EACH HVAC UNIT, NOMANUFACTORY NAME PLATES WITH UNIT RATING, LISTING, OR MODEL NUMBER
OPEN 03/07/2020 03/07/2020
 
005 (272) EQUIPMENT GROUNDING CONDUCTOR NOT PROPERLY INSTALLED
(ALL FLOORS) ART. 250. 148 CONTRACTOR USING PRE WIRED LEVITONRECEPTACLES, GROUND EQUIPMENT CONDUCTOR PROVIDED WITH DEVICE ISTAPED AND NOT TERMINATED TO METAL BOX, ALL ROOMS ALL RECEPTACLES,CONTRACTOR LIKE TO UPLOAD DOCUMENTS PROVING THIS IS RECOMMENDEDINSTALLATION METHOD BY MANUFACTURE
RSLV 03/07/2020 03/07/2020 03/11/2020
 
006 (999) OTHER
(ALL FLOORS)CONTRACTOR NEEDS TO CORRECT FILING, NO HVAC EQUIPMENT FILED,
RSLV 03/07/2020 03/07/2020 02/11/2021



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order