| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
2 |
(2) 80A |
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
2 |
(2) 2/3 |
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
2 |
125A |
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 63) |
RECEPTACLE OUTLETS NOT IN SUFFICIENT NUMBER (FLOOR: 003) 210.52, RECEPTACLE NOT PROVIDED FOR WALL SPACE. |
RSLV |
01/14/2019 |
01/14/2019 |
02/22/2019 |
| |
| 002 |
( 53) |
GFCI HAS NOT BEEN PROVIDED (ALL FLOORS)210.8, AT BATH RM, MIRROR RECEPTACLE ARE NOT GFCI PROTECTED,THRU-OUT, |
RSLV |
01/14/2019 |
01/14/2019 |
02/22/2019 |
| |
| 003 |
(999) |
OTHER (ALL FLOORS)410.144, LED LIGHT, TRANSFORMER MUST BE ACCESSIBLE AFTERINSTALLATION, THRU-OUT. |
RSLV |
01/14/2019 |
01/14/2019 |
02/22/2019 |
| |
| 004 |
( 29) |
OUTLET BOXES ARE NOT COVERED (BASEMENT) 314.25, JUNCTION BOX FOR FEEDER ARE NOT COVER. |
RSLV |
01/14/2019 |
01/14/2019 |
02/22/2019 |
| |
| 005 |
( 46) |
PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY (BASEMENT) 408.4, FEEDER PANEL, NO DIRECTORY PROVIDED. |
RSLV |
01/14/2019 |
01/14/2019 |
02/22/2019 |