BIS Menu  |  Plumb. Inspections  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M404267
Premises: 14 EXCHANGE PLACE MANHATTAN BIN: 1000830     Block: 27   Lot: 7502
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 20 EXCHANGE PL Census Tract:   7 Health Area:  7700
HANOVER STREET Admin Area:   M - MANHATTAN Inspection Area:   W
NEW YORK, NY 10005 Community Board:   101
DOB Cross Street(s):   HANOVER STREET,    WILLIAM STREET
Status:   C - JOB IS SIGNED OFF 02/08/2020
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  11/16/2017 2:51 PM
Application Entered:   11/16/2017 Job Start Date:   12/15/2017
Last Change:   02/08/2020 Job End Date:   12/15/2019
Appointment Status:   
Last Inspection By:   ADAM ADAMSKI       On     02/07/2020      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 009891 Licensee Name: WILLIAM T WHALEN
Firm: 003886 Firm Name: NEE ELECTRICAL, LLC
Firm Phone: 718-349-4756  Firm Address: 47-55 37TH STREET LONG ISLAND CITY NY 11101 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
Total Fee:  $290.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JOSEPH ALEXANDER
Owner Business Name: RBNB20 OWNER LLC
Authorized Representative:  KATHERINE EDDERS
Relationship To Owner:   ELEVATOR COMPANY


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  2  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 01/17/2020
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  2 NEW ELEVATORS

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M404267
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 10/18/2019 10/18/2019 AGF V (55) (8)
INSPECTION COMMENTS: FAIL ... ELEVATOR CAR #'S ;1P50378 AND 1P50377 . INSPECTION NOT COMPLETED . CONTRACTOR COULD NOT LOCATE MAIN FUSING FOR KNIFE SWITCHES IN MACHINE RM. TOP OF CARS , AND PITS , AND MAIN FEEDER FUSING SHALL BE INSPECTED .
 
(2) 01/17/2020 01/17/2020 ASK V R (60) (2)
INSPECTION COMMENTS: FAIL OBJECTION ISSUED.
 
(3) 02/07/2020 02/08/2020 ASK C R (40) (0)
INSPECTION COMMENTS: PASS.

OBJECTION FOR APPLICATION #: M404267
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(MEZZANINE-ONLY 1 MEZZANINE IN BUILDING)MACHINE RM. ELEVATOR , MOTORS CONDUCTORS UNDER SIZED PER TABLE430.250, 620
RSLV 10/18/2019 10/18/2019 01/17/2020
 
002 (999) OTHER
(MEZZANINE-ONLY 1 MEZZANINE IN BUILDING)MOTOR CONDUCTORS PHASE MARKINGS IN CORRECT , ART. 200
RSLV 10/18/2019 10/18/2019 01/17/2020
 
003 (999) OTHER
(MEZZANINE-ONLY 1 MEZZANINE IN BUILDING)NO GFCI FOR RECEPTACLE IN MACHINE RM. ART. 620
RSLV 10/18/2019 10/18/2019 01/17/2020
 
004 (999) OTHER
(MEZZANINE-ONLY 1 MEZZANINE IN BUILDING)TOP OF CARS AND PITS NOT INSPECTED , NO TIME LEFT
RSLV 10/18/2019 10/18/2019 01/17/2020
 
005 (999) OTHER
(MEZZANINE-ONLY 1 MEZZANINE IN BUILDING)OPEN SLICE BOX FOR CONTROL WIRES , ART. 314
RSLV 10/18/2019 10/18/2019 01/17/2020
 
006 (999) OTHER
(MEZZANINE-ONLY 1 MEZZANINE IN BUILDING)CONTRACTOR COULD NOT LOCATE MAIN FUSING FOR KNIFE SWITCHES INMACHINE RM.
RSLV 10/18/2019 10/18/2019 01/17/2020
 
007 (999) OTHER
(MEZZANINE-ONLY 1 MEZZANINE IN BUILDING) NO PANEL ON APP ( 100 AMP )
RSLV 10/18/2019 10/18/2019 01/17/2020
 
008 (999) OTHER
(MEZZANINE-ONLY 1 MEZZANINE IN BUILDING)ALL OBJ. FOR CAR #'S ;1P50378 , AND 1P50377 .
RSLV 10/18/2019 10/18/2019 01/17/2020
 
009 (999) OTHER
(ALL FLOORS) ELEV. PIT GFCI NOT PROVIDED 620.24
RSLV 01/17/2020 01/17/2020 02/07/2020
 
010 (999) OTHER
(ALL FLOORS) ELEVATOR PIT GFCI AND PUMP OUTLET NOT WORKING 620.24
RSLV 01/17/2020 01/17/2020 02/07/2020



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Plumb. Inspections  |  Electrical Inspection Work Order  |  Back