| BUILDING OVERVIEW |
Are Feeders Being Installed? : No |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
2 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(999) |
OTHER (MEZZANINE-ONLY 1 MEZZANINE IN BUILDING)MACHINE RM. ELEVATOR , MOTORS CONDUCTORS UNDER SIZED PER TABLE430.250, 620 |
RSLV |
10/18/2019 |
10/18/2019 |
01/17/2020 |
| |
| 002 |
(999) |
OTHER (MEZZANINE-ONLY 1 MEZZANINE IN BUILDING)MOTOR CONDUCTORS PHASE MARKINGS IN CORRECT , ART. 200 |
RSLV |
10/18/2019 |
10/18/2019 |
01/17/2020 |
| |
| 003 |
(999) |
OTHER (MEZZANINE-ONLY 1 MEZZANINE IN BUILDING)NO GFCI FOR RECEPTACLE IN MACHINE RM. ART. 620 |
RSLV |
10/18/2019 |
10/18/2019 |
01/17/2020 |
| |
| 004 |
(999) |
OTHER (MEZZANINE-ONLY 1 MEZZANINE IN BUILDING)TOP OF CARS AND PITS NOT INSPECTED , NO TIME LEFT |
RSLV |
10/18/2019 |
10/18/2019 |
01/17/2020 |
| |
| 005 |
(999) |
OTHER (MEZZANINE-ONLY 1 MEZZANINE IN BUILDING)OPEN SLICE BOX FOR CONTROL WIRES , ART. 314 |
RSLV |
10/18/2019 |
10/18/2019 |
01/17/2020 |
| |
| 006 |
(999) |
OTHER (MEZZANINE-ONLY 1 MEZZANINE IN BUILDING)CONTRACTOR COULD NOT LOCATE MAIN FUSING FOR KNIFE SWITCHES INMACHINE RM. |
RSLV |
10/18/2019 |
10/18/2019 |
01/17/2020 |
| |
| 007 |
(999) |
OTHER (MEZZANINE-ONLY 1 MEZZANINE IN BUILDING) NO PANEL ON APP ( 100 AMP ) |
RSLV |
10/18/2019 |
10/18/2019 |
01/17/2020 |
| |
| 008 |
(999) |
OTHER (MEZZANINE-ONLY 1 MEZZANINE IN BUILDING)ALL OBJ. FOR CAR #'S ;1P50378 , AND 1P50377 . |
RSLV |
10/18/2019 |
10/18/2019 |
01/17/2020 |
| |
| 009 |
(999) |
OTHER (ALL FLOORS) ELEV. PIT GFCI NOT PROVIDED 620.24 |
RSLV |
01/17/2020 |
01/17/2020 |
02/07/2020 |
| |
| 010 |
(999) |
OTHER (ALL FLOORS) ELEVATOR PIT GFCI AND PUMP OUTLET NOT WORKING 620.24 |
RSLV |
01/17/2020 |
01/17/2020 |
02/07/2020 |