BIS Menu  |  Pre-BIS PA CO Query By Bin  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M404134
Premises: 20 HUDSON YARDS MANHATTAN BIN: 1088961     Block: 702   Lot: 7501
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 500 W 33RD ST Census Tract:   99 Health Area:  5500
5-7TH & 10TH FLOORS Admin Area:   M - MANHATTAN Inspection Area:   Q
NEW YORK, NY 10001 Community Board:   104
Special Place Name:   NEIMAN MARCUS
DOB Cross Street(s):    10 AVENUE,    HUDSON BOULEVARD EAST
Status:   C - JOB IS SIGNED OFF 06/17/2019
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  11/14/2017 2:41 PM
Application Entered:   11/14/2017 Job Start Date:   11/14/2017
Last Change:   06/17/2019 Job End Date:   11/01/2018
Appointment Status:   
Last Inspection By:   ADAM ADAMSKI       On     04/12/2019      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011188 Licensee Name: GARY A FISHBONE
Firm: 001253 Firm Name: ROBERT B SAMUELS, INC
Firm Phone: 212-645-5150  Firm Address: 132 WEST 36TH STREET, 2ND FL NEW YORK NY 10018 

Other Licensees and Firms:
License # Licensee Name Firm # Firm Name Type
009336 SAMUELS, DAVID I 001253 ROBERT B SAMUELS, INC RESPONSIBLE REP

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $5,040.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: TW NY PROPERTIES LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  2  (2) #2
B. Over #2 to 1/0  4  (3) #1, (1) 1/0
C. Over 1/0 to 250 MCM  7  (7) #3/0
D. Over 250 MCM  42  (29) 55MCM, (10) 350MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  15  (15) 42 CKT
D. 3 Phase Over 225 AMPS  101  (101) 42 CKT
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
005    590  481  35  152  2125  35  221  11  65  540 
006    670  580  38  214  2610  43  220  14  87  690 
007    596  291  37  248  2239  59  310  20  773 
010                       
Buildings Total 1856  1352  110  616  6974     751     172     2003 
Total Units : 13834 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 03/06/2019
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  73923- T. PAGLIARO

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M404134
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 03/06/2019 03/06/2019 CBK V (390) (8)
INSPECTION COMMENTS: SEE OBJECTIONS DETAILS.
 
(2) 04/12/2019 04/12/2019 ASK C R (110) (0)
INSPECTION COMMENTS: PASS.

OBJECTION FOR APPLICATION #: M404134
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 15) FLEXIBLE CORDS USED AS PERMANENT WIRING METHOD
(FLOOR: 006)ZIP CORD FOR LAMP IN DINING ROOM PASSING THROUGH DESK, T-OUT
RSLV 03/06/2019 03/06/2019 04/12/2019
 
002 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(FLOOR: 006) ROOM LAYOUT.
RSLV 03/06/2019 03/06/2019 04/12/2019
 
003 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(FLOOR: 006) BREAKER SIZE.
RSLV 03/06/2019 03/06/2019 04/12/2019
 
004 (999) OTHER
(FLOOR: 006) PANNIC BAR NEEDED ON DOORS. 110.26(C)(2)
RSLV 03/06/2019 03/06/2019 04/12/2019
 
005 (999) OTHER
(FLOOR: 006) 150KVA TRANSFORMER OVER-FUSE ON THE PRIMER. 45025
RSLV 03/06/2019 03/06/2019 04/12/2019
 
006 (999) OTHER
(FLOOR: 006)DISCONNECTS FOR KITCHEN DISHWASHERS NOT READILY, AND NO WORKINGCLEARANCE. 404.8/110.26
RSLV 03/06/2019 03/06/2019 04/12/2019
 
007 ( 53) GFCI HAS NOT BEEN PROVIDED
(ALL FLOORS) RECEPTACLES IN BATHROOM AREAS NOT GFCI PROTECTED.
RSLV 03/06/2019 03/06/2019 04/12/2019
 
008 (999) OTHER
(ALL FLOORS)DEED UL LISTING FOR FIXED IN PLACE FURNITURE LIGHTING. 110.2
RSLV 03/06/2019 03/06/2019 04/12/2019



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Pre-BIS PA CO Query By Bin  |  Electrical Inspection Work Order  |  Back