| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
1 |
200A |
| C. 201 Up to 600 AMPS |
2 |
400A |
| D. 601 Up to 1200 AMPS |
3 |
2-800A,1-1200A |
| E. Over 1200 AMPS |
1 |
2000A |
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
20 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
1 |
1 SET 3/0 |
| D. Over 250 MCM |
10 |
10 SETS 600MCM |
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
20 |
40AMP-2 POLE |
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(123) |
SERVICE DISCONNECTS ARE NOT PROPERLY GROUPED/LABELED (CELLAR) ART. 230.2(E) SERVICE SWITCH #6 IS NOT IDENTIFIED |
OPEN |
07/18/2019 |
07/18/2019 |
|
| |
| 002 |
(176) |
INSTALLATION DOES NOT MEET CODE REQUIREMENTS (CELLAR) ART. 110.16 EQUIPMENT MISSING ARC FLASH LABELS |
OPEN |
07/18/2019 |
07/18/2019 |
|
| |
| 003 |
(176) |
INSTALLATION DOES NOT MEET CODE REQUIREMENTS (CELLAR)AMEND 110.2(B) 3/0 GROUND ELECTRODE BUS NOT INSTALLED AS PER REV. #2PLANS AT THE 2,000 AMP S.S. |
OPEN |
07/18/2019 |
07/18/2019 |
|
| |
| 004 |
(176) |
INSTALLATION DOES NOT MEET CODE REQUIREMENTS (CELLAR)AMEND 110.2(B) LOAD SIDE OF THE 2,000 AMP S.S. NOT INSTALLED AS PERREV. #2 PLANS |
OPEN |
07/18/2019 |
07/18/2019 |
|
| |
| 005 |
(176) |
INSTALLATION DOES NOT MEET CODE REQUIREMENTS (CELLAR)AMEND 110.2 RETAIL STORE FUSING NOT INSTALLED AS PER REV. #2 PLANS. |
OPEN |
07/18/2019 |
07/18/2019 |
|
| |
| 006 |
(176) |
INSTALLATION DOES NOT MEET CODE REQUIREMENTS (CELLAR)AMEND 110.2 FEEDS FOR RETAIL STORE AND "BUTTERFIELDS" DISCONNECTSNOT SIZED AS PER REV. # 2 PLANS. |
OPEN |
07/18/2019 |
07/18/2019 |
|
| |
| 007 |
(176) |
INSTALLATION DOES NOT MEET CODE REQUIREMENTS (CELLAR)ART. 230.7 SERVICE AND LOAD SIDE WIRING ARE LOCATED IN THE SAME WIREWAY OF S.S. # 5 |
OPEN |
07/18/2019 |
07/18/2019 |
|
| |
| 008 |
(176) |
INSTALLATION DOES NOT MEET CODE REQUIREMENTS (CELLAR) ART. 250.24 NEUTRAL IS NOT GROUNDED IN S.S. #5 |
OPEN |
07/18/2019 |
07/18/2019 |
|
| |
| 009 |
(176) |
INSTALLATION DOES NOT MEET CODE REQUIREMENTS (CELLAR)AMEND 110.2 LOAD SIDE OF THE 60 AMP FIRE ALARM SERVICE SWITCH IS NOTINSTALLED AS PER REV #2 PLANS |
OPEN |
07/18/2019 |
07/18/2019 |
|
| |
| 010 |
(176) |
INSTALLATION DOES NOT MEET CODE REQUIREMENTS (CELLAR)ART. 314.29 GROUNDING AND MAIN BONDING JUMPER IN S.S. #4 ARE NOTACCESSIBLE |
OPEN |
07/18/2019 |
07/18/2019 |
|
| |
| 011 |
(176) |
INSTALLATION DOES NOT MEET CODE REQUIREMENTS (CELLAR)AMEND 110.2 60 AMP FIRE ALARM SERVICE SWITCH NOT INSTALLED AS PERREV #2 PLANS |
OPEN |
07/18/2019 |
07/18/2019 |
|
| |
| 012 |
(176) |
INSTALLATION DOES NOT MEET CODE REQUIREMENTS (CELLAR)AMEND 110.2 P.L.P. PANEL FUSING NOT INSTALLED AS PER REV #2 APPROVEDPLANS |
OPEN |
07/18/2019 |
07/18/2019 |
|
| |
| 013 |
(176) |
INSTALLATION DOES NOT MEET CODE REQUIREMENTS (CELLAR)ART. 240.21 "BUTTERFIELDS" 400 AMP TAP NOT INSTALLED AS PER THE 25'TAP RULE SPECS. |
OPEN |
07/18/2019 |
07/18/2019 |
|
| |
| 014 |
(176) |
INSTALLATION DOES NOT MEET CODE REQUIREMENTS (CELLAR) AMEND 110.2 FIRE PUMP IS NOT FUSED AS PER THE REV. #2 PLANS |
OPEN |
07/18/2019 |
07/18/2019 |
|