Premises: 114 MULBERRY STREET MANHATTAN BIN: 1090225     Block: 205   Lot: 8
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 114 MULBERRY ST Census Tract:   41 Health Area:  6800
CEL, 1-7, ROOF Admin Area:   M - MANHATTAN Inspection Area:   U
NEW YORK, NY 10013 Community Board:   102
Related Job Number:    121191334
DOB Cross Street(s):   CANAL STREET,    HESTER STREET
Status:   C - JOB IS SIGNED OFF 05/14/2019
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  11/10/2017 3:15 PM
Application Entered:   11/10/2017 Job Start Date:   11/10/2017
Last Change:   05/14/2019 Job End Date:   11/09/2019
Appointment Status:   
Last Inspection By:   RACEWICZ, TOMASZ       On     05/07/2019      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011878 Licensee Name: EDGAR LEVENSTEIN
Firm: 003500 Firm Name: CONTACT PLUS ELEC'L CORP
Firm Phone: 718-254-0291  Firm Address: 2922 SHELL ROAD BROOKLYN NY 11224 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
7 - HVAC WIRING
T - TEMPORARY LIGHT & POWER
Total Fee:  $2,539.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Commercial/Residential (2  Stores, 23 Apartments)
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: ERIC BRODY
Owner Business Name: 114 MS OWNER LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  2  200 AMP
C. 201 Up to 600 AMPS  2  800 AMP
D. 601 Up to 1200 AMPS  1  1200 AMP
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  25  2 AWG, 1/0 AWG
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  6  500 MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  23  100 AMP
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  5  200 AMP
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL    40      16  40     
001    40      40     
002    44      20  44     
003    42      20  42         
004    42      20  42         
005    42      20  42         
006    40      22  40         
007    32      22  32             
ROF               
Buildings Total 330      150  330     11     28      
Total Units : 849 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 23 #4-Wire 2 #10-Wire 1
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 11/10/2017 Notice: 1 - FIRST NOTICE 03/22/2019
Power Issued: 11/10/2017 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M404019
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 03/07/2019 03/07/2019 TOR V (155) (10)
INSPECTION COMMENTS: FAIL
 
(2) 03/22/2019 03/22/2019 DWB V Y (45) (3)
INSPECTION COMMENTS: APPS DOSE NOT MATCH INSTALL, OBJECTION ISSUED.
 
(3) 05/07/2019 05/07/2019 TOR C R (20) (0)
INSPECTION COMMENTS: PASS

OBJECTION FOR APPLICATION #: M404019
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 19) DEFECTIVE WIRING IS IN USE
(ALL FLOORS) LIGHTS IN ELECTRIC ROOM ON MOTION SENSOR
RSLV 03/07/2019 03/07/2019 03/22/2019
 
002 (999) OTHER
(ALL FLOORS) NEED UPDATE APP FOR 7 SERVICE SW INCLUDING FIRE PUMP
RSLV 03/07/2019 03/07/2019 05/07/2019
 
003 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
(CELLAR) T-OUT SERVICE SW (WIRE GA NOT ADEQUATE )
RSLV 03/07/2019 03/07/2019 05/07/2019
 
004 (101) CONDUCTORS AND/OR EQUIPMENT USED IS NOT APPROVED
(CELLAR) JACKIE PUMP TAP FROM FIRE PUMP.
RSLV 03/07/2019 03/07/2019 03/22/2019
 
005 (125) PROTECTION OF CONDUCTORS NOT INSTALLED AS PER CODE
(CELLAR) PANEL PP-H
RSLV 03/07/2019 03/07/2019 05/07/2019
 
006 ( 19) DEFECTIVE WIRING IS IN USE
(CELLAR) 2 WATER MAINS NEED BOND TOGETHER (WIRE SIZE NOT ADEQUATE)
RSLV 03/07/2019 03/07/2019 03/22/2019
 
007 ( 19) DEFECTIVE WIRING IS IN USE
(CELLAR)PROPER IDENTIFICATION OF ELECTRICAL EQUIPMENT NOT PROVIDED T-OUT
RSLV 03/07/2019 03/07/2019 03/22/2019
 
008 (999) OTHER
(CELLAR) ARC FLASH WARNING LABELS NOT PROVIDED 110.116 T-OUT
RSLV 03/07/2019 03/07/2019 03/22/2019
 
009 (999) OTHER
(CELLAR) SERVICE SWITCHES GROUND NOT AS PER 250.66 T-OUT
RSLV 03/07/2019 03/07/2019 05/07/2019
 
010 ( 19) DEFECTIVE WIRING IS IN USE
(ROOF) ALL OUTDOOR RECEPTACLES MISSING IN USE COVERS T-OUT
RSLV 03/07/2019 03/07/2019 03/22/2019
 
011 ( 53) GFCI HAS NOT BEEN PROVIDED
(ALL FLOORS)210.8, RECEPTACLE INSTALL IN KITCHEN ARE ARE NOT GFCI PROTECTED.
RSLV 03/22/2019 03/22/2019 05/07/2019
 
012 (229) SPLICE BOXES NOT ACCESSIBLE
(BASEMENT)314.29, RISER JUNCTION BOXES INSTALL IN CEILING ARE NOT ACCESSIBLE.
RSLV 03/22/2019 03/22/2019 05/07/2019
 
013 (999) OTHER
(CELLAR) ELECTRICAL SERVICE EQUIPMENT INSTALL, NEED ADVISORY BOARD.
RSLV 03/22/2019 03/22/2019 05/07/2019