| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
2 |
200 AMP |
| C. 201 Up to 600 AMPS |
2 |
800 AMP |
| D. 601 Up to 1200 AMPS |
1 |
1200 AMP |
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
25 |
2 AWG, 1/0 AWG |
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
6 |
500 MCM |
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
23 |
100 AMP |
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
5 |
200 AMP |
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 19) |
DEFECTIVE WIRING IS IN USE (ALL FLOORS) LIGHTS IN ELECTRIC ROOM ON MOTION SENSOR |
RSLV |
03/07/2019 |
03/07/2019 |
03/22/2019 |
| |
| 002 |
(999) |
OTHER (ALL FLOORS) NEED UPDATE APP FOR 7 SERVICE SW INCLUDING FIRE PUMP |
RSLV |
03/07/2019 |
03/07/2019 |
05/07/2019 |
| |
| 003 |
( 1) |
SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER (CELLAR) T-OUT SERVICE SW (WIRE GA NOT ADEQUATE ) |
RSLV |
03/07/2019 |
03/07/2019 |
05/07/2019 |
| |
| 004 |
(101) |
CONDUCTORS AND/OR EQUIPMENT USED IS NOT APPROVED (CELLAR) JACKIE PUMP TAP FROM FIRE PUMP. |
RSLV |
03/07/2019 |
03/07/2019 |
03/22/2019 |
| |
| 005 |
(125) |
PROTECTION OF CONDUCTORS NOT INSTALLED AS PER CODE (CELLAR) PANEL PP-H |
RSLV |
03/07/2019 |
03/07/2019 |
05/07/2019 |
| |
| 006 |
( 19) |
DEFECTIVE WIRING IS IN USE (CELLAR) 2 WATER MAINS NEED BOND TOGETHER (WIRE SIZE NOT ADEQUATE) |
RSLV |
03/07/2019 |
03/07/2019 |
03/22/2019 |
| |
| 007 |
( 19) |
DEFECTIVE WIRING IS IN USE (CELLAR)PROPER IDENTIFICATION OF ELECTRICAL EQUIPMENT NOT PROVIDED T-OUT |
RSLV |
03/07/2019 |
03/07/2019 |
03/22/2019 |
| |
| 008 |
(999) |
OTHER (CELLAR) ARC FLASH WARNING LABELS NOT PROVIDED 110.116 T-OUT |
RSLV |
03/07/2019 |
03/07/2019 |
03/22/2019 |
| |
| 009 |
(999) |
OTHER (CELLAR) SERVICE SWITCHES GROUND NOT AS PER 250.66 T-OUT |
RSLV |
03/07/2019 |
03/07/2019 |
05/07/2019 |
| |
| 010 |
( 19) |
DEFECTIVE WIRING IS IN USE (ROOF) ALL OUTDOOR RECEPTACLES MISSING IN USE COVERS T-OUT |
RSLV |
03/07/2019 |
03/07/2019 |
03/22/2019 |
| |
| 011 |
( 53) |
GFCI HAS NOT BEEN PROVIDED (ALL FLOORS)210.8, RECEPTACLE INSTALL IN KITCHEN ARE ARE NOT GFCI PROTECTED. |
RSLV |
03/22/2019 |
03/22/2019 |
05/07/2019 |
| |
| 012 |
(229) |
SPLICE BOXES NOT ACCESSIBLE (BASEMENT)314.29, RISER JUNCTION BOXES INSTALL IN CEILING ARE NOT ACCESSIBLE. |
RSLV |
03/22/2019 |
03/22/2019 |
05/07/2019 |
| |
| 013 |
(999) |
OTHER (CELLAR) ELECTRICAL SERVICE EQUIPMENT INSTALL, NEED ADVISORY BOARD. |
RSLV |
03/22/2019 |
03/22/2019 |
05/07/2019 |