BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M403873
Premises: 505 8 AVENUE MANHATTAN BIN: 1013575     Block: 759   Lot: 37
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 505 8 AV Census Tract:   111 Health Area:  5500
3RD FLOOR Admin Area:   M - MANHATTAN Inspection Area:   Q
NEW YORK, NY 10018 Community Board:   104
Special Place Name:   JUMPSTART
DOB Cross Street(s):   WEST 35 STREET,    WEST 36 STREET
Status:   C - JOB IS SIGNED OFF 09/26/2018
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  11/08/2017 9:39 AM
Application Entered:   11/08/2017 Job Start Date:   11/09/2017
Last Change:   09/26/2018 Job End Date:   11/01/2018
Appointment Status:   
Last Inspection By:   ALBERT HANSON       On     03/13/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012795 Licensee Name: DAREN A DODSON
Firm: 004416 Firm Name: G ENERGY SOLTN AND SVCS I
Firm Phone: 800-697-7620  Firm Address: 1061 WASHINGTON AVENUE BRONX NY 10456 

Other Licensees and Firms:
License # Licensee Name Firm # Firm Name Type
012588 RASHEED, RAYMAN 004416 G ENERGY SOLTN AND SVCS I RESPONSIBLE REP

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $107.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: ZEFF PERPEPAJ
Owner Business Name: JUMP START
Authorized Representative:  RAYMAN RASHEED
Relationship To Owner:   CONTRACTOR


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
003    26  29  12     
Buildings Total   26  29        12      
Total Units : 81 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 02/15/2018
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  N/A

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M403873
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/09/2018 02/09/2018 TOR N (17) (0) Y
INSPECTION COMMENTS: CALLED CONTRACTOR NO SHOW
 
(2) 02/15/2018 02/15/2018 EDB V (45) (2)
INSPECTION COMMENTS: SEE ATTACHMENT.
 
(3) 03/13/2018 03/13/2018 ATH J Y (0) (0)
INSPECTION COMMENTS: CERTIFIED - OBJ-18-000003585
 
(4) 03/13/2018 03/13/2018 ATH C R (0) (0)
INSPECTION COMMENTS: CERTIFIED - OBJ-18-000003586

OBJECTION FOR APPLICATION #: M403873
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
(FLOOR: 003)LFMC OVER 18" LONG AM. 605.6
RSLV 02/15/2018 02/15/2018 03/13/2018
 
002 (999) OTHER
(FLOOR: 003) LFMC NOT PROPERLY SECURED 350.30
RSLV 02/15/2018 02/15/2018 03/13/2018



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order