BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M403857
Premises: 38 EAST 52 STREET MANHATTAN BIN: 1076267     Block: 1287   Lot: 28
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 40 E 52ND ST Census Tract:   102 Health Area:  4800
ALL FLOORS SERVED, MR Admin Area:   M - MANHATTAN Inspection Area:   L
NEW YORK, NY 10022 Community Board:   105
Special Place Name:   A BANK
DOB Cross Street(s):   MADISON AVENUE,    PARK AVENUE
Status:   C - JOB IS SIGNED OFF 03/04/2021
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  11/07/2017 4:53 PM
Application Entered:   11/07/2017 Job Start Date:   11/15/2017
Last Change:   03/04/2021 Job End Date:   11/15/2020
Appointment Status:   
Last Inspection By:   RACEWICZ, TOMASZ       On     03/04/2021      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011986 Licensee Name: ANTHONY LUCIANO
Firm: 003652 Firm Name: JAM ELECTRICAL CORP
Firm Phone: 212-265-0142  Firm Address: 1133 6TH AVE 28TH FLOOR NEW YORK NY 10036 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
Total Fee:  $1,163.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: KERRY BENDER
Owner Business Name: RUDIN MGMT
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  5  ELEVATORS
B. Each Additional 10 Floors Or Less  6  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 05/14/2020
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  ALTERATION OF ELEVATOR DEVICE 1P33329-1P33333 BY ELEVATOR COMPANY IN CONJUNCTION WITH EBN2249/17(273018E). ELEVATOR CONTROL AND LOAD SIDE WIRING ONLY BY ELEVATOR EMPLOYEES CONFORMING TO STANDARDS OF THE ELECTRICAL CODE. POWER TO CONTROL, 110V LIGHTING, MR, PIT GFCI BY OTHERS. L0541(701)

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M403857
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 05/13/2020 05/14/2020 MJD V (45) (3)
INSPECTION COMMENTS: FAIL, OBJECTIONS ISSUED, ON SITE CONTACT CORCORAN JOSEPH, ELEVATORS DEVICE # A1-1P33329, A2-1P33330, A3-1P33331, A4-1P33332, A5-1P33333
 
(2) 03/04/2021 03/04/2021 TOR C R (30) (0)
INSPECTION COMMENTS: PASS

OBJECTION FOR APPLICATION #: M403857
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (154) THE OVERCURRENT DEVICE HAS NOT BEEN PROPERLY SIZED
(ROOF)ART. 110.3 100 AMP DISCONNECT SWITCHES FUSED WITH 150 AMP ELEVATORA3, A4, A5,
RSLV 05/13/2020 05/13/2020 03/04/2021
 
002 ( 42) BUSHINGS ARE MISSING OR LOOSE
(ROOF) ART. 300.4 BUSHINGS NOT PROVIDED MOTOR SIDE T-OUT
RSLV 05/13/2020 05/13/2020 03/04/2021
 
003 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
(ROOF)ART. 110.3 240 V DISCONNECT SWITCHES USED ON 480 V ALL ELEVATORS
RSLV 05/13/2020 05/13/2020 03/04/2021



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.