| BUILDING OVERVIEW |
Are Feeders Being Installed? : No |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
4 |
1 #8, 2 #4, 1 #3 |
| B. Over #2 to 1/0 |
1 |
#1/0 |
| C. Over 1/0 to 250 MCM |
1 |
#3/0 |
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
3 |
1 @ 100 & 1 @ 225 AMPS |
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 15) |
FLEXIBLE CORDS USED AS PERMANENT WIRING METHOD (ALL FLOORS) FLEX CORD USED FOR DISPLAY BOARDS. |
RSLV |
01/18/2019 |
01/18/2019 |
04/25/2019 |
| |
| 002 |
( 25) |
ARMORED CABLES ARE NOT PROPERLY TERMINATED (ALL FLOORS) MCS NOT TERMINATED BOXES IN DISPLAY BOARDS. |
RSLV |
01/18/2019 |
01/18/2019 |
04/25/2019 |
| |
| 003 |
( 29) |
OUTLET BOXES ARE NOT COVERED (ALL FLOORS)NO PLATES ON RECEPTACLES IN IT ROOM AND IN DISPLAY BOARDS. |
RSLV |
01/18/2019 |
01/18/2019 |
04/25/2019 |
| |
| 004 |
(999) |
OTHER (ALL FLOORS) NO LISTING ON DISPLAY BOARDS T-OUT. 110.2 |
RSLV |
01/18/2019 |
01/18/2019 |
04/25/2019 |
| |
| 005 |
(999) |
OTHER (GROUND FLOOR) NO CLEARANCE IN FRONT OF PANELS. 110.26 |
RSLV |
01/18/2019 |
01/18/2019 |
04/25/2019 |
| |
| 006 |
(999) |
OTHER (GROUND FLOOR)NO SERVICE LIGHT PROVIDED FOR TRANSFORMERS ON PLATFORM ABOVECEILING. 110.26 |
RSLV |
01/18/2019 |
01/18/2019 |
04/25/2019 |
| |
| 007 |
( 30) |
OUTLET BOXES ARE NOT SECURED (GROUND FLOOR) J-BOXES INSIDE DISPLAY NOT SECURED. |
RSLV |
04/25/2019 |
04/25/2019 |
05/24/2019 |
| |
| 008 |
(999) |
OTHER (GROUND FLOOR)NEC 110.2 NO LISTING FOR DISPLAYS INSTALLED WITH MULTIPLE DRIVERS,SWITCHES, RECEPTACLES IN ENCLOSURE. |
RSLV |
04/25/2019 |
04/25/2019 |
05/24/2019 |