BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M403556
Premises: 6 PARK AVENUE MANHATTAN BIN: 1017105     Block: 864   Lot: 35
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 10 PARK AVE. Census Tract:   74 Health Area:  5200
APT 8G & 8H Admin Area:   M - MANHATTAN Inspection Area:   P
NEW YORK, NY 10016 Community Board:   106
DOB Cross Street(s):   EAST 34 STREET,    EAST 35 STREET
Status:   C - JOB IS SIGNED OFF 12/16/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  10/31/2017 3:45 PM
Application Entered:   10/31/2017 Job Start Date:   10/31/2017
Last Change:   12/16/2017 Job End Date:   10/31/2018
Appointment Status:   
Last Inspection By:   ALGERNON CHARLES       On     12/13/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 009113 Licensee Name: MARTIN WEINSTEIN
Firm: 000796 Firm Name: JOSEPH WEINSTEIN ELECTRIC
Firm Phone: 718-843-5555  Firm Address: 94-24 88TH STREET CORP OZONE PARK NY 11416 

Work Started or Filed by Others: YES
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $42.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: 10 PARK AVE. TENANTS CORP
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
008  8G               
008  8H                 
Buildings Total   10                
Total Units : 19 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 11/15/2017
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  REF: APPLICATION NO. M393494. 3 SMOKE DETECTORS

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M403556
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 11/15/2017 11/15/2017 VTC V (57) (4)
INSPECTION COMMENTS: FAIL
 
(2) 12/13/2017 12/13/2017 AYC C R (55) (0)
INSPECTION COMMENTS: PASS

OBJECTION FOR APPLICATION #: M403556
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (128) NEUTRAL IS GROUNDED BEYOND LOAD SIDE OF SERVICE SWITCH
(FLOOR: 008) NEUTRAL BONDED AT SUB PANEL
RSLV 11/15/2017 11/15/2017 12/13/2017
 
002 ( 19) DEFECTIVE WIRING IS IN USE
(FLOOR: 008) GROUNDS NOT TERMINATED AT PANEL
RSLV 11/15/2017 11/15/2017 12/13/2017
 
003 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
(FLOOR: 008) AFCI NOT PROVIDED FOR NEW CIRCUITS
RSLV 11/15/2017 11/15/2017 12/13/2017
 
004 (999) OTHER
(FLOOR: 008) SEPERATE CIRCUIT NOT PROVIDED FOR AC 210.11 NYC AMD.
RSLV 11/15/2017 11/15/2017 12/13/2017



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back