| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
6 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
15 |
|
| B. Over #2 to 1/0 |
264 |
|
| C. Over 1/0 to 250 MCM |
191 |
|
| D. Over 250 MCM |
102 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
98 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
294 |
|
| C. 3 Phase Up to 225 AMPS |
77 |
|
| D. 3 Phase Over 225 AMPS |
65 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (FLOOR: 011)ROOM LAY OUT HAS CABINETS AS DISTRIBUTION BOARDS THAT DO NOT REFLECTSWITCHES BUT SWITCHES ARE PRESENT. |
RSLV |
07/20/2019 |
07/20/2019 |
08/08/2020 |
| |
| 002 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (FLOOR: 011) FIRE PUMP FUSING DOES NOT MATCH DRAWING |
RSLV |
07/20/2019 |
07/20/2019 |
08/08/2020 |
| |
| 003 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (FLOOR: 011)TD-DS-11-2 HAS SPARES IN POSITIONS OTHER THATN LOCATION ON DRAWING |
RSLV |
07/20/2019 |
07/20/2019 |
06/04/2020 |
| |
| 004 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (FLOOR: 067)PANEL#-TD EO DS 67 1 B-HAS IMPROPER FUSING NOT MATCHING DRAWING.HAS 400 INSTALLED 225 ON DRAWING. |
RSLV |
07/20/2019 |
07/20/2019 |
08/08/2020 |
| |
| 005 |
(124) |
TAP CONDUCTORS ARE NOT WITHIN 10 FT OR WITHIN 25 FT AS PER CODE (ALL FLOORS)ALL JOCKEY PUMP TAPS ARE TAPPED FROM FIRE PUMP AND IN ADDITION NOTAS PER DRAWING. |
RSLV |
07/20/2019 |
07/20/2019 |
11/14/2020 |
| |
| 006 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (ALL FLOORS)SWITCH BOARD TD-SS-11-1' HAS A BUS BAR AT DIFFERENT SIZES ON DRAWINGTHEN INSTALLED. |
RSLV |
07/20/2019 |
07/20/2019 |
02/05/2021 |
| |
| 007 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (ALL FLOORS) FIRE ALARM DISCONNECT FUSING IS NOT AS PER DRAWING. |
RSLV |
07/20/2019 |
07/20/2019 |
08/08/2020 |
| |
| 008 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (ALL FLOORS)ALL FIRE PUMPS ARE FED WITH MI CABLE THEN SPLICED IN TROUGH TODIFFERENT WIRE(THHN) OF DIFFERENT SIZE NOT REFLECTED ON DRAWING. |
RSLV |
07/20/2019 |
07/20/2019 |
11/14/2020 |
| |
| 009 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (FLOOR: 001) HVAC DIS SW NOT ON DRAWING. |
RSLV |
08/08/2020 |
08/08/2020 |
11/14/2020 |
| |
| 010 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (FLOOR: 011) SWITCH BOARD ID-SS-11-1, NOT SHOW ON DRAWING. |
RSLV |
08/08/2020 |
08/08/2020 |
02/05/2021 |
| |
| 011 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (FLOOR: 068) 30 AMP FIRE DIS SW NOT AS PER DRAWING. |
RSLV |
08/08/2020 |
08/08/2020 |
11/14/2020 |
| |
| 012 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (ALL FLOORS) ALL FLR, 68 FLR, FIRE ALARM DIS SW, NOT AS PER DRAWING. |
RSLV |
08/08/2020 |
08/08/2020 |
11/14/2020 |
| |
| 013 |
(176) |
INSTALLATION DOES NOT MEET CODE REQUIREMENTS (FLOOR: 001)AM 408.60(C) NOT PROVIDED WARNING LABEL 277/480V ( JOCKEY PUMP DISCSW ) FIRE PUMP ROOM |
RSLV |
11/14/2020 |
11/14/2020 |
02/05/2021 |
| |
| 014 |
(176) |
INSTALLATION DOES NOT MEET CODE REQUIREMENTS (FLOOR: 001)110.16 NOT PROVIDED ARC FLASH HAZARD LABEL ( JOCKEY PUMP - DISC SW )- FIRE PUMP ROOM) |
RSLV |
11/14/2020 |
11/14/2020 |
02/05/2021 |
| |
| 015 |
(123) |
SERVICE DISCONNECTS ARE NOT PROPERLY GROUPED/LABELED (FLOOR: 011)AM 230.70(B) - 110.22 T-OUT ALL SERVICE SW ( ELECTRICAL ROOM) |
RSLV |
11/14/2020 |
11/14/2020 |
02/05/2021 |
| |
| 016 |
(281) |
GROUNDING ELECTRODE CONDUCTOR IS NOT CONTINUOUS (FLOOR: 011)250.64(E) THE BONDING JUMPER FOR A GEC RACEWAY SHALL BE SAME SIZE ASOR LARGER THAN , THE ENCLOSED GEC. ( GEC @ COLLECTOR BARTERMINATION) ( ELECTRICAL ROOM) |
RSLV |
11/14/2020 |
11/14/2020 |
02/05/2021 |
| |
| 017 |
(176) |
INSTALLATION DOES NOT MEET CODE REQUIREMENTS (ALL FLOORS)110.22 MARKING SHALL BE OF SUFFICIENT DURABILITY ( T-OUT JOCKEY PUMPDISC SW ) ( FIRE PUMP ROOM) |
RSLV |
11/14/2020 |
11/14/2020 |
02/05/2021 |
| |
| 018 |
(308) |
CONDUCTORS ARE NOT PROPERLY INSTALLED/TERMINATED (ALL FLOORS)110.14- 110.3(B) TWO CONDUCTORS UNDER LUG RATED FOR A SINGLECONDUCTORS ( T-OUT JOCKEY PUMP DISC SW - EGC TERMINATION) ( FIREPUMP ROOM) |
RSLV |
11/14/2020 |
11/14/2020 |
02/05/2021 |