Electrical Application Details for App #: M403516
Premises: 11 HUDSON YARDS MANHATTAN BIN: 1091045     Block: 702   Lot: 4
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 553 W 30 ST Census Tract:   99
CELL,1-70,ROOF Admin Area:   M - MANHATTAN Inspection Area:   Q
NEW YORK, NY 10001 Community Board:   104
Related Job Number:    121184208
DOB Cross Street(s):   HIGH LINE,    11 AVENUE
Status:   C - JOB IS SIGNED OFF 03/19/2021
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   10/31/2017 Job Start Date:   10/16/2017
Last Change:   03/19/2021 Job End Date:   03/01/2019
Appointment Status:   
Last Inspection By:   SHERON MEYERS       On     02/05/2021      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011062 Licensee Name: ROBERT CHAIKIN
Firm: 002415 Firm Name: A.S.R. ELEC'L CONTR'G INC
Firm Phone: 917-432-2700  Firm Address: 969 THIRD AVENUE #4F NEW YORK NY 10022 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
7 - HVAC WIRING
L - LIGHTING WORK
Total Fee:  $5,040.00
Hurricane Sandy Damage:   No
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   Yes
Job Number:  121184208
Building Used As:   Z - Commercial/Residential (0  Stores, 392 Apartments)
Special Cert Approval:  
Advisory Board Approval:   REQUIRED
Advisory Board Categories:      K - 1000 KVA SERVICE                            
Advisory Board Approval #:   54134     Submittal #: 16A0491CO  
Owner / Occup: GREGORY GUSHEE
Owner Business Name: ERY TENANT LCC C/O RELATE
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  6  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  15  
B. Over #2 to 1/0  264  
C. Over 1/0 to 250 MCM  191  
D. Over 250 MCM  102  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  98  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  294  
C. 3 Phase Up to 225 AMPS  77  
D. 3 Phase Over 225 AMPS  65  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
SC1    51    88  88      30 
CEL    35    10  62  26         
BAS    38    90  19  348  120 
001    20    36      75 
002                       
003    22    65  19  105  60 
004    28    18  15         
005                 
006                   
007                   
008                     
009    12    37      90 
010    18    62  26  90 
011    12  54    14  143  42  274  150 
012                 
013    12            500 
014    12               
015              30 
016    12               
017                 
018    12            500 
019    12    12             
020                   
021                   
022                30 
023    11    16          30 
024                 
025    12            500 
026    12               
027                 
028    12               
029    12               
030                 
031    12            500 
032    12               
033              30 
034    12               
035    12               
036    46    10  136  46  613  60 
037    51    16  140  42  1427  10  412 
038      11          113 
039    16            113 
040                 
041    12               
042    12            500 
043              30 
044                 
045    12               
046                 
047                 
048    12            500 
049                 
050    12            30 
051                 
052                 
053    12               
054    12            500 
055                 
056      20  43         
057      14      30 
058                 
059    12               
060    12            500 
061                 
062    12               
063                 
064              30 
065    12               
066                 
067    10    55  18  343  180 
068    48    99  46  525  30 
069    40    39  11  318  96  30 
070      17      57  90 
ROF          12             
Buildings Total 206  854    241  1451     4157     161     5883 
Total Units : 12953 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 2
Existing Meters 0 + New Meters 2 - Removed Meters 0 = Total Meters 2

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 10/31/2017 Notice: 1 - FIRST NOTICE 11/16/2020
Power Issued: 10/31/2017 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M403516
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/20/2019 07/23/2019 PMK V (450) (8)
INSPECTION COMMENTS: FAIL-WORKED THRU MULTIPLE PARTS OF ADVISORY BOARD, STILL NEED TO INSPECT GENERATOR AND LIFE SAFETY EQUIPMENT. ALSO DRAWING #D-1606-27850-E CONTRACTOR HAD A REVISION 3 AND I ONLY HAD A REVISION 1.
 
(2) 06/04/2020 06/05/2020 CBK J Y (210) (0)
INSPECTION COMMENTS: NEED UPDATED DRAWING AS PREVIOUS INSPECTOR NOTED. GENERATOR ROOM WAS INSPECTED, LAYOUT OF ROOM AND EQUIPMENTS NOT MATCHING DRAWINGS.NOT COMPLETE
 
(3) 08/08/2020 08/10/2020 DWB V Y (160) (4)
INSPECTION COMMENTS: INSPECTION COMPLETE, CONTRACTOR TO EITHER REVISE DRAWING OR FIX OBJECTIONS (AS PER TOM IN THE DOB OFFICE)
 
(4) 11/14/2020 11/16/2020 CDX V Y (180) (6)
INSPECTION COMMENTS: FAIL. COMPLETE INSPECTION . OBJECTION PARTLY REMOVED. ADVISORY BOARD CAL # 54134 - SUB # 16A0491
 
(5) 02/05/2021 02/05/2021 SWR C R (95) (0)
INSPECTION COMMENTS: INSPECTION COMPLETE.

OBJECTION FOR APPLICATION #: M403516
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(FLOOR: 011)ROOM LAY OUT HAS CABINETS AS DISTRIBUTION BOARDS THAT DO NOT REFLECTSWITCHES BUT SWITCHES ARE PRESENT.
RSLV 07/20/2019 07/20/2019 08/08/2020
 
002 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(FLOOR: 011) FIRE PUMP FUSING DOES NOT MATCH DRAWING
RSLV 07/20/2019 07/20/2019 08/08/2020
 
003 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(FLOOR: 011)TD-DS-11-2 HAS SPARES IN POSITIONS OTHER THATN LOCATION ON DRAWING
RSLV 07/20/2019 07/20/2019 06/04/2020
 
004 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(FLOOR: 067)PANEL#-TD EO DS 67 1 B-HAS IMPROPER FUSING NOT MATCHING DRAWING.HAS 400 INSTALLED 225 ON DRAWING.
RSLV 07/20/2019 07/20/2019 08/08/2020
 
005 (124) TAP CONDUCTORS ARE NOT WITHIN 10 FT OR WITHIN 25 FT AS PER CODE
(ALL FLOORS)ALL JOCKEY PUMP TAPS ARE TAPPED FROM FIRE PUMP AND IN ADDITION NOTAS PER DRAWING.
RSLV 07/20/2019 07/20/2019 11/14/2020
 
006 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(ALL FLOORS)SWITCH BOARD TD-SS-11-1' HAS A BUS BAR AT DIFFERENT SIZES ON DRAWINGTHEN INSTALLED.
RSLV 07/20/2019 07/20/2019 02/05/2021
 
007 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(ALL FLOORS) FIRE ALARM DISCONNECT FUSING IS NOT AS PER DRAWING.
RSLV 07/20/2019 07/20/2019 08/08/2020
 
008 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(ALL FLOORS)ALL FIRE PUMPS ARE FED WITH MI CABLE THEN SPLICED IN TROUGH TODIFFERENT WIRE(THHN) OF DIFFERENT SIZE NOT REFLECTED ON DRAWING.
RSLV 07/20/2019 07/20/2019 11/14/2020
 
009 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(FLOOR: 001) HVAC DIS SW NOT ON DRAWING.
RSLV 08/08/2020 08/08/2020 11/14/2020
 
010 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(FLOOR: 011) SWITCH BOARD ID-SS-11-1, NOT SHOW ON DRAWING.
RSLV 08/08/2020 08/08/2020 02/05/2021
 
011 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(FLOOR: 068) 30 AMP FIRE DIS SW NOT AS PER DRAWING.
RSLV 08/08/2020 08/08/2020 11/14/2020
 
012 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(ALL FLOORS) ALL FLR, 68 FLR, FIRE ALARM DIS SW, NOT AS PER DRAWING.
RSLV 08/08/2020 08/08/2020 11/14/2020
 
013 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(FLOOR: 001)AM 408.60(C) NOT PROVIDED WARNING LABEL 277/480V ( JOCKEY PUMP DISCSW ) FIRE PUMP ROOM
RSLV 11/14/2020 11/14/2020 02/05/2021
 
014 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(FLOOR: 001)110.16 NOT PROVIDED ARC FLASH HAZARD LABEL ( JOCKEY PUMP - DISC SW )- FIRE PUMP ROOM)
RSLV 11/14/2020 11/14/2020 02/05/2021
 
015 (123) SERVICE DISCONNECTS ARE NOT PROPERLY GROUPED/LABELED
(FLOOR: 011)AM 230.70(B) - 110.22 T-OUT ALL SERVICE SW ( ELECTRICAL ROOM)
RSLV 11/14/2020 11/14/2020 02/05/2021
 
016 (281) GROUNDING ELECTRODE CONDUCTOR IS NOT CONTINUOUS
(FLOOR: 011)250.64(E) THE BONDING JUMPER FOR A GEC RACEWAY SHALL BE SAME SIZE ASOR LARGER THAN , THE ENCLOSED GEC. ( GEC @ COLLECTOR BARTERMINATION) ( ELECTRICAL ROOM)
RSLV 11/14/2020 11/14/2020 02/05/2021
 
017 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(ALL FLOORS)110.22 MARKING SHALL BE OF SUFFICIENT DURABILITY ( T-OUT JOCKEY PUMPDISC SW ) ( FIRE PUMP ROOM)
RSLV 11/14/2020 11/14/2020 02/05/2021
 
018 (308) CONDUCTORS ARE NOT PROPERLY INSTALLED/TERMINATED
(ALL FLOORS)110.14- 110.3(B) TWO CONDUCTORS UNDER LUG RATED FOR A SINGLECONDUCTORS ( T-OUT JOCKEY PUMP DISC SW - EGC TERMINATION) ( FIREPUMP ROOM)
RSLV 11/14/2020 11/14/2020 02/05/2021