Electrical Application Details for App #: M403273
Premises: 1120 5 AVENUE MANHATTAN BIN: 1047101     Block: 1505   Lot: 1
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 1120 5TH AV Census Tract:   160.01 Health Area:  2820
APT 11B Admin Area:   M - MANHATTAN Inspection Area:   J
NEW YORK, NY 10128 Community Board:   108
DOB Cross Street(s):   EAST 93 STREET,    EAST 94 STREET
Status:   C - JOB IS SIGNED OFF 02/07/2018
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  10/25/2017 2:51 PM
Application Entered:   10/25/2017 Job Start Date:   10/25/2017
Last Change:   02/07/2018 Job End Date:   10/25/2018
Appointment Status:   
Last Inspection By:   ALBERT HANSON       On     02/07/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010587 Licensee Name: HARRY FRENKEL
Firm: 002697 Firm Name: APOLLO ELECTRIC INC.
Firm Phone: 212-627-2561  Firm Address: 127 WEST 24TH ST,5TH FL STE#A NEW YORK NY 10011 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
7 - HVAC WIRING
Total Fee:  $193.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: EDWARD HANNINGTON
Owner Business Name: HANNINGTON ENGINEERING CO
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  2  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
011  65  58  15  20  65             
Buildings Total 65  58  15  20  65                
Total Units : 223 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 02/01/2018
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  N/A

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M403273
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/01/2018 02/01/2018 MQY V (62) (2)
INSPECTION COMMENTS: ISSUED OBJECTIONS
 
(2) 02/07/2018 02/07/2018 ATH J Y (0) (0)
INSPECTION COMMENTS: CERTIFIED - OBJ-18-000001769
 
(3) 02/07/2018 02/07/2018 ATH C R (0) (0)
INSPECTION COMMENTS: CERTIFIED - OBJ-18-000001770

OBJECTION FOR APPLICATION #: M403273
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(FLOOR: 011) FEEDER SPLICE NOT ACCESSIBLE (314.29)(110.26)
RSLV 02/01/2018 02/01/2018 02/07/2018
 
002 (999) OTHER
(FLOOR: 011) LAMPHOLDER IN CLOTHES CLOSET T-OUT (410.16)
RSLV 02/01/2018 02/01/2018 02/07/2018



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.