| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
4 |
2-4000A,2-1200A |
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
36 |
#6 |
| B. Over #2 to 1/0 |
400 |
1/0 |
| C. Over 1/0 to 250 MCM |
156 |
144#250,12#2/0,6#3/0 |
| D. Over 250 MCM |
20 |
20#600,8#350 |
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
59 |
12-60,10-100,36-200 |
| D. 3 Phase Over 225 AMPS |
4 |
3-400,1-600 |
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
INSP ID |
FIELD DATE |
DISP DATE |
INSP ID |
FLD DISP |
OBJ DISP |
ENRG REC |
TIME INSP |
REINSP DATE |
NEW OBJ |
APPT FLAG |
| |
| (1) |
11/24/2017 |
11/27/2017 |
EDB |
V |
|
|
(300) |
|
(11) |
|
| INSPECTION COMMENTS:
|
CONTRACTOR NEED TO REVISED THE DRAWINGS . SEE ATTACHMENT.
|
| |
| (2) |
11/16/2018 |
11/16/2018 |
EDB |
J |
X |
|
(130) |
|
(0) |
Y |
| INSPECTION COMMENTS:
|
CONTRACTOR NOT READY FOR INSPECTION (DRAWING INCORRECT). SEE ATTACHMENT.
|
| |
| (3) |
10/11/2019 |
10/11/2019 |
EDB |
V |
X |
|
(85) |
|
(1) |
|
| INSPECTION COMMENTS:
|
CONTRACTOR HAS DIFFERENT DRAWING.
|
| |
| (4) |
03/09/2020 |
03/23/2020 |
TUR |
V |
X |
|
(1) |
|
(1) |
|
| INSPECTION COMMENTS:
|
NO PROGRESS ON JOB , CONTRACTOR MUST ATTEND TO THE OPEN OBJECTIONS PRIOR TO REQUESTING ANOTHER INSPECTION TODAY IS 03/21/2020 NOTE ADDED BY INSPECTOR SCHULER MANHATTAN OFFICE 1212 323 7268 , SEE NOTE ABOUT THE APP NEEDS TO BE UPDATES , (IF ANYTHING HAS TO COME OFF THE APP ENTIRE APP TO BE REFILLED , IF ADDING ONLY OPEN NEW APP FOR THE (+)
|
| |
| (5) |
08/22/2020 |
08/25/2020 |
SWR |
V |
Y |
|
(180) |
|
(1) |
|
| INSPECTION COMMENTS:
|
FAIL. INSPECTION COMPLETE. OBJECTION ISSUED. CONTRACTOR NEEDS TO FILE NEW APP FOR ADDITIONAL DEVICES AND INCLUDE APP # M403235, CALENDER # 51708 SUBMITTAL # PLEASE CALL ASSISTANT CHIEF T SCHULER. 1 212 323 7268.
|
| |
| (6) |
08/25/2020 |
09/04/2020 |
TUR |
V |
R |
|
(1) |
|
(1) |
|
| INSPECTION COMMENTS:
|
INSPECTIONS COMPLETE, ONE S/C OBJECTION REMAINS LABELING
|
| |
| (7) |
09/10/2020 |
09/10/2020 |
TSO |
C |
R |
|
(0) |
|
(0) |
|
| INSPECTION COMMENTS:
|
CERTIFIED - OBJ-20-000020145
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 1) |
SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER (SUB-CELLAR)S. SW(S) 3,4,5,6 AND 7 NOT BONDED 250.92 |
RSLV |
11/24/2017 |
11/24/2017 |
08/22/2020 |
| |
| 002 |
( 19) |
DEFECTIVE WIRING IS IN USE (SUB-CELLAR) MISSING NEUTRAL IN S. SW(S) 3,4,5,6 AND 7215.4, 300.3B,20 |
RSLV |
11/24/2017 |
11/24/2017 |
08/25/2020 |
| |
| 003 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (SUB-CELLAR)LAY OUT OF THE ROOM, FUSES AND INSTALLATION NOT PER DRAWING.AM. 110.2 |
RSLV |
11/24/2017 |
11/24/2017 |
08/22/2020 |
| |
| 004 |
(261) |
ELECTRICAL CLOSETS/SERVICE ROOM IS USED FOR OTHER PURPOSES (SUB-CELLAR)EL. RM. USED AS STORAGE AM. 110.25 |
RSLV |
11/24/2017 |
11/24/2017 |
08/22/2020 |
| |
| 005 |
( 5) |
SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY (SUB-CELLAR)BUILDING HAS TWO WATER MAINS 250.50,52 |
RSLV |
11/24/2017 |
11/24/2017 |
08/22/2020 |
| |
| 006 |
( 56) |
ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED (SUB-CELLAR)S. SW. #7 (STEAM) OVER 6'7" 240.24 |
RSLV |
11/24/2017 |
11/24/2017 |
08/22/2020 |
| |
| 007 |
( 56) |
ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED (SUB-CELLAR)S. SW. #2 : LINE AND LOAD UPSIDE DOWN 110.2,3 |
RSLV |
11/24/2017 |
11/24/2017 |
08/22/2020 |
| |
| 008 |
(999) |
OTHER (SUB-CELLAR)S. SW(S) NOT PROPERLY IDENTIFIED 230.66,70B |
RSLV |
11/24/2017 |
11/24/2017 |
08/25/2020 |
| |
| 009 |
(999) |
OTHER (SUB-CELLAR)NO ARC FLASH WARNING ON NEW INSTALLATION 110.16 |
RSLV |
11/24/2017 |
11/24/2017 |
08/22/2020 |
| |
| 010 |
(999) |
OTHER (SUB-CELLAR)NO FIRE STOP IN PENETRATION OF WALL 300.21 |
RSLV |
11/24/2017 |
11/24/2017 |
08/22/2020 |
| |
| 011 |
(999) |
OTHER (SUB-CELLAR)ATS IN EL. SERVICE ROOM 1 RCNY 12-01, BC2702 |
RSLV |
11/24/2017 |
11/24/2017 |
08/22/2020 |
| |
| 012 |
(999) |
OTHER (CELLAR)ADMINISTRATIVE CONTRACTOR NEED UPDATE APPLICATION FOR S.SW(S), FEEDERS AND ADDITIONAL EQUIPMENT |
RSLV |
10/11/2019 |
10/11/2019 |
08/22/2020 |
| |
| 013 |
(176) |
INSTALLATION DOES NOT MEET CODE REQUIREMENTS (ALL FLOORS) NO PROGRESS ON JOB , CONTRACTOR MUST ATTEND TO THE OPEN OBJECTIONS PRIOR TO REQUESTING ANOTHER INSPECTION TODAY IS 03/21/2020 NOTE ADDED BY INSPECTOR SCHULER MANHATTAN OFFICE 1212 323 7268 ,SEE NOTE ABOUT THE APP NEEDS TO BE UPDATES , (IF ANYTHING HAS TO COME OFF THE APP ENTIRE APP TO BE REFILLED , IF ADDING ONLY OPEN NEW AP |
RSLV |
03/09/2020 |
03/09/2020 |
08/25/2020 |
| |
| 014 |
(176) |
INSTALLATION DOES NOT MEET CODE REQUIREMENTS (ALL FLOORS)CONTRACTOR TO FILE NEW APPLICATION TO SHOW ADDITIONAL DEVICES,TOTAL 10 SERVICE SWITCHES AND TOTAL 1 FIRE ALARM SERVICE SWITCH 100AMP UP TO 225 AMPS. |
RSLV |
08/22/2020 |
08/22/2020 |
08/25/2020 |
| |
| 015 |
(176) |
INSTALLATION DOES NOT MEET CODE REQUIREMENTS (SUB-CELLAR)FLOOR SUB:999-OTHER S. SW(S) NOT PROPERLY IDENTIFIED 230.66,70BOPEN ? ? 11/27/2017 |
RSLV |
08/25/2020 |
08/25/2020 |
09/10/2020 |