BIS Menu  |  Plumb. Inspections  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M403060
Premises: 432 PARK AVENUE MANHATTAN BIN: 1088817     Block: 1292   Lot: 33
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 432 PARK AV Census Tract:   112.02 Health Area:  4800
85TH Admin Area:   M - MANHATTAN Inspection Area:   L
NEW YORK, NY 10022 Community Board:   105
Special Place Name:   PARKLIGHT LLC
DOB Cross Street(s):   EAST 56 STREET,    EAST 57 STREET
Status:   C - JOB IS SIGNED OFF 03/05/2020
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  10/20/2017 10:39 AM
Application Entered:   10/20/2017 Job Start Date:   10/23/2017
Last Change:   03/05/2020 Job End Date:   10/23/2018
Appointment Status:   
Last Inspection By:   SHERON MEYERS       On     02/11/2020      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010341 Licensee Name: WARREN OSTROFF
Firm: 002946 Firm Name: WARREN OSTROFF ELEC., INC
Firm Phone: 718-323-5200  Firm Address: 401 PARK AVENUE S. STE 861 NEW YORK NY 10016 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
7 - HVAC WIRING
L - LIGHTING WORK
Total Fee:  $264.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   Yes
Job Number:  123347887
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: PARKLIGHT LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  1  (4) 1/0 1 1/2" EMT
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  (1) 3PHASE 42 CIR 225A
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
085    48  163    61  282  16  32         
Buildings Total 48  163    61  282     32           
Total Units : 586 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 02/03/2020
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M403060
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/03/2020 02/03/2020 SWR V (55) (6)
INSPECTION COMMENTS: FAIL. OBJECTION ISSUED. PARTIAL INSPECTION (1 PANEL AND KITCHEN) FULL INSPECTION IS NEEDED THROUGH OUT APT.
 
(2) 02/11/2020 02/12/2020 SWR C R (30) (0)
INSPECTION COMMENTS: PASS WITH APP # M00309511

OBJECTION FOR APPLICATION #: M403060
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(FLOOR: 085) PANEL SCHEDULE T-OUT. ART. 408.4
RSLV 02/03/2020 02/03/2020 02/11/2020
 
002 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(FLOOR: 085) DISCONNECTING MEANS FOR HOOD. ART. 422.30
RSLV 02/03/2020 02/03/2020 02/11/2020
 
003 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(FLOOR: 085)CONTRACTOR NEEDS TO SEND AFFIDAVIT OF SUPPORT LETTER FOR ALL FIXEDAPPLIANCES (KITCHEN) STATING THAT THEY ARE WIRED ACCORDING TO CODE,PERMIT NUMBER AND APT NUMBER TO BE SHOWN IN LETTER.
RSLV 02/03/2020 02/03/2020 02/11/2020
 
004 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(FLOOR: 085) DISHWASHER OUTLET IS NOT ACCESSIBLE. ART 314.29
RSLV 02/03/2020 02/03/2020 02/11/2020
 
005 (999) OTHER
(FLOOR: 085)CONTRACTOR NEEDS TO FILE NEW APPLICATION WITH SCOPE OF WORK (DETAILAND DESCRIPTION).
RSLV 02/03/2020 02/03/2020 02/11/2020
 
006 (999) OTHER
(FLOOR: 085)CONTRACTOR NEEDS TO CORRECT FOR APP (MOTORS AND PANELS).
RSLV 02/03/2020 02/03/2020 02/11/2020



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Plumb. Inspections  |  Electrical Inspection Work Order  |  Back