NYC Department of Buildings
Electrical Application Details for App #: M403012
Premises: 102 NORFOLK STREET MANHATTAN BIN: 1004299     Block: 353   Lot: 49
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 102 NORFOLK ST Census Tract:   14.02 Health Area:  7400
APT. 9 Admin Area:   M - MANHATTAN Inspection Area:   V
NEW YORK, NY 10002 Community Board:   103
DOB Cross Street(s):   DELANCEY STREET,    RIVINGTON STREET
Status:   C - JOB IS SIGNED OFF 01/18/2022
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  10/19/2017 2:11 PM
Application Entered:   10/19/2017 Job Start Date:   10/19/2017
Last Change:   01/18/2022 Job End Date:   10/19/2019
Appointment Status:   
Last Inspection By:   SCHULER, THOMAS       On     01/17/2022      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011372 Licensee Name: STEVEN DENNISON
Firm: 003326 Firm Name: DENNISON ELECTRIC CORP
Firm Phone: 718-803-6421  Firm Address: 37-31 58TH STREET WOODSIDE NY 11377 

Work Started or Filed by Others: YES
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $93.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: OMER ZWICKEL
Owner Business Name: SMA EQUITIES
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  3 # 4 THHN WIRE
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  100 AMPS 220 VOLTS
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
003  30  30    15  30             
Buildings Total 30  30    15  30                
Total Units : 105 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: C - CALL TO OFFICE 03/15/2021
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  INSTALL GENERAL WIRING, LIGHTS, SWITCHES, RECEPTACLES, PANEL, RISER.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M403012
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 01/12/2018 01/12/2018 CLC V (40) (1)
INSPECTION COMMENTS: INSPECTION FAIL
 
(2) 01/31/2018 01/31/2018 PHG N (30) (0) Y
INSPECTION COMMENTS: NO SHOW
 
(3) 03/13/2021 03/15/2021 JRP V X (30) (6)
INSPECTION COMMENTS: THIS HOMEOWNER INSPECTION IS BEEN PERFORM WITH WCK ELECTRIC, CONTRACTOR NEEDS TO OBTAIN NEW ELECTRICAL PERMIT TO SUPERSEDE APP AND CURE ALL OBJECTIONS. INSPECTION INCOMPLETE
 
(4) 01/17/2022 01/18/2022 TUR C R (1) (0)
INSPECTION COMMENTS: SEE REQ COMMENT SEE SUBSEQUENT APP M00644725I1EL

OBJECTION FOR APPLICATION #: M403012
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(FLOOR: 004) APT 9. NO TWO CKTS PROVIDED ON COUNTER 210.52 B 1
RSLV 01/12/2018 01/12/2018 01/17/2022
 
002 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(FLOOR: 003)ALL LIGHT FIXTURES T/O THE APARTMENT NOT PROPERLY GROUNDED 410.46
RSLV 03/13/2021 03/13/2021 01/17/2022
 
003 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(FLOOR: 003) HVAC UNIT NOT ACCESSIBLE 110.13(B)
RSLV 03/13/2021 03/13/2021 01/17/2022
 
004 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(FLOOR: 003)NEED TO PROVIDE GROUNDING TERMINAL BAR IN PANEL 408.40, 250.118
RSLV 03/13/2021 03/13/2021 01/17/2022
 
005 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(FLOOR: 003)EXHAUST FAN IN KITCHEN NOT LISTED FOR COOKING AREAS 110.3(B)
RSLV 03/13/2021 03/13/2021 01/17/2022
 
006 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(FLOOR: 003)EXHAUST FAN WITH SHOWER AREA NOT GFCI PROTECTED 410.10(D),110.3(FOLLOW SPECS)
RSLV 03/13/2021 03/13/2021 01/17/2022
 
007 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(FLOOR: 003)LIGHT FIXTURE IN BATHROOM NOT LISTED FOR DAMP LOCATIONS 410.10(D)
RSLV 03/13/2021 03/13/2021 01/17/2022