Electrical Application Details for App #: M402829
Premises: 14 EXCHANGE PLACE MANHATTAN BIN: 1000830     Block: 27   Lot: 7502
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 20 EXCHANGE PL Census Tract:   7 Health Area:  7700
GROUND FLOOR Admin Area:   M - MANHATTAN Inspection Area:   W
NEW YORK, NY 10005 Community Board:   101
DOB Cross Street(s):   HANOVER STREET,    WILLIAM STREET
Status:   C - JOB IS SIGNED OFF 12/10/2019
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  10/16/2017 2:13 PM
Application Entered:   10/16/2017 Job Start Date:   10/17/2017
Last Change:   12/10/2019 Job End Date:   12/29/2017
Appointment Status:   
Last Inspection By:   ADAM ADAMSKI       On     09/17/2019      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011796 Licensee Name: MICHAEL ALICANTI
Firm: 004717 Firm Name: TRI CAM ELECL VENTURES LL
Firm Phone: 917-939-9520  Firm Address: 58-35 UTOPIA PARKAWAY SUITE 3A FRESH MEADOWS NY 11365 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
Total Fee:  $165.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: LOUIS CULOT
Owner Business Name: RBNB 20 OWNER LLC C/O DTH
Authorized Representative:  LOUIS CULOT
Relationship To Owner:   REPRESENTATIVE


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  1  1 FLR. SINGLE PERSON LIFT
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
GND                   
Buildings Total                   
Total Units : 3 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: C - CALL TO OFFICE 09/09/2019
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M402829
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 08/21/2019 08/21/2019 CDX V (15) (3)
INSPECTION COMMENTS: FAIL. ELEVATOR ID : 1W7201
 
(2) 09/09/2019 09/09/2019 DWB V X (55) (4)
INSPECTION COMMENTS: OBJECTION ISSUED.
 
(3) 09/17/2019 09/17/2019 ASK C R (40) (0)
INSPECTION COMMENTS: PASS.

OBJECTION FOR APPLICATION #: M402829
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
(CELLAR)CELLAR ( A LEVEL) 408.4 PANEL DIRECTORY NEEDED UPDATE ( ELECTRICALPANEL )
RSLV 08/21/2019 08/21/2019 09/17/2019
 
002 (999) OTHER
(CELLAR)CELLAR ( A LEVEL) 210.4(B) MISSING HANDLE TIES ( OCPD FOR ELEVATOR)( ELECTRICAL PANEL)
RSLV 08/21/2019 08/21/2019 09/17/2019
 
003 (999) OTHER
(CELLAR)CELLAR ( A LEVEL ) 620.55 OCPD ARE NOT LOCKABLE ( ELECTRICALPANEL)
RSLV 08/21/2019 08/21/2019 09/17/2019
 
004 (999) OTHER
(GROUND FLOOR)AM 725.136, LOW VOLTAGE AND HIGH VOLTAGE RAN IN IN SAME RACEWAY/ ATJUNCTION NEXT TO LIFT CONTROLLER.
RSLV 09/09/2019 09/09/2019 09/17/2019
 
005 (999) OTHER
(GROUND FLOOR)620.51(C), AT LIFT INSTALLED, DISCONNECT SWITCH NOT READILYACCESSIBLE WITH IN SITE.
RSLV 09/09/2019 09/09/2019 09/17/2019
 
006 (999) OTHER
(GROUND FLOOR)LIFT CONTROLLER NOT ACCESSIBLE/ TO INSPECT CONDUCTOR TERMINATION.
RSLV 09/09/2019 09/09/2019 09/17/2019
 
007 (250) NO OTHER CONDUCTORS IN RACEWAY
(SUB-CELLAR)230.7, AT LIFT DIS SW, LINE AND LOAD RAN IN SAME RACEWAY.
RSLV 09/09/2019 09/09/2019 09/17/2019



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.