| BUILDING OVERVIEW |
Are Feeders Being Installed? : No |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
1 |
1 FLR. SINGLE PERSON LIFT |
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 46) |
PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY (CELLAR)CELLAR ( A LEVEL) 408.4 PANEL DIRECTORY NEEDED UPDATE ( ELECTRICALPANEL ) |
RSLV |
08/21/2019 |
08/21/2019 |
09/17/2019 |
| |
| 002 |
(999) |
OTHER (CELLAR)CELLAR ( A LEVEL) 210.4(B) MISSING HANDLE TIES ( OCPD FOR ELEVATOR)( ELECTRICAL PANEL) |
RSLV |
08/21/2019 |
08/21/2019 |
09/17/2019 |
| |
| 003 |
(999) |
OTHER (CELLAR)CELLAR ( A LEVEL ) 620.55 OCPD ARE NOT LOCKABLE ( ELECTRICALPANEL) |
RSLV |
08/21/2019 |
08/21/2019 |
09/17/2019 |
| |
| 004 |
(999) |
OTHER (GROUND FLOOR)AM 725.136, LOW VOLTAGE AND HIGH VOLTAGE RAN IN IN SAME RACEWAY/ ATJUNCTION NEXT TO LIFT CONTROLLER. |
RSLV |
09/09/2019 |
09/09/2019 |
09/17/2019 |
| |
| 005 |
(999) |
OTHER (GROUND FLOOR)620.51(C), AT LIFT INSTALLED, DISCONNECT SWITCH NOT READILYACCESSIBLE WITH IN SITE. |
RSLV |
09/09/2019 |
09/09/2019 |
09/17/2019 |
| |
| 006 |
(999) |
OTHER (GROUND FLOOR)LIFT CONTROLLER NOT ACCESSIBLE/ TO INSPECT CONDUCTOR TERMINATION. |
RSLV |
09/09/2019 |
09/09/2019 |
09/17/2019 |
| |
| 007 |
(250) |
NO OTHER CONDUCTORS IN RACEWAY (SUB-CELLAR)230.7, AT LIFT DIS SW, LINE AND LOAD RAN IN SAME RACEWAY. |
RSLV |
09/09/2019 |
09/09/2019 |
09/17/2019 |