BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M402722
Premises: 38 BROAD STREET MANHATTAN BIN: 1078985     Block: 24   Lot: 7501
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 40 BROAD ST Census Tract:   9 Health Area:  7700
STREET Admin Area:   M - MANHATTAN Inspection Area:   W
NEW YORK, NY 10004 Community Board:   101
DOB Cross Street(s):   EXCHANGE PLACE,    BEAVER STREET
Status:   C - JOB IS SIGNED OFF 04/10/2018
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  10/13/2017 6:04 AM
Application Entered:   10/13/2017 Job Start Date:   10/13/2017
Last Change:   04/10/2018 Job End Date:   10/01/2018
Appointment Status:   
Last Inspection By:   RACEWICZ, TOMASZ       On     04/04/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012502 Licensee Name: JOSEPH INGARGIOLA
Firm: 004314 Firm Name: EASTERN ELEC'L TECHNOLOGI
Firm Phone: 718-805-2123  Firm Address: 112-08 101ST AVENUE RICHMOND HILL NY 11419 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $176.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   K - Store
Store / Other:   COFFEE SHOP
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: PHILIP FINSTEEN
Owner Business Name: JOE AND THE JUICE
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  1  400 AMP -84 CIRCUIT
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
EPT    99  50    99             
Buildings Total 99  50    99                
Total Units : 256 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 03/06/2018
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M402722
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 03/05/2018 03/06/2018 STP V (60) (6)
INSPECTION COMMENTS: FAIL. CONTRACTOR COULD NOT OPEN 400 AMP BUCKET FOR PROTECTION OF PANEL. TERMINATIONS IN WATER HEATER LOCKED AND NO ACCESS TO 60 AMP SWITCH FOR AC. MOTORS HEATERS AND FEEDER NOT FILED FOR. THIS JOB MAY BE ADVISORY BOARD FROM 400 AMP BUCKET WITH TWO POINTS OF ENTRY. TROUGH NOT INSPECTED ABOVE PANEL.
 
(2) 04/04/2018 04/05/2018 TOR C R (30) (0)
INSPECTION COMMENTS: PASS

OBJECTION FOR APPLICATION #: M402722
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(GROUND FLOOR) DIRECTORY FOR PANEL 408.4
RSLV 03/05/2018 03/05/2018 04/04/2018
 
002 (999) OTHER
(GROUND FLOOR) ARC FLASH STICKERS FOR PANEL 110.16
RSLV 03/05/2018 03/05/2018 04/04/2018
 
003 (999) OTHER
(GROUND FLOOR) WIRE NOT MARKED OFF 110 AMP CKT BKR 310.11
RSLV 03/05/2018 03/05/2018 04/04/2018
 
004 (999) OTHER
(GROUND FLOOR) WATER HEATER DISCONNECT NO BOND 250
RSLV 03/05/2018 03/05/2018 04/04/2018
 
005 (999) OTHER
(GROUND FLOOR) WATER HEATER DISCONNECT MILLS CUT PHASES 110.14
RSLV 03/05/2018 03/05/2018 04/04/2018
 
006 (999) OTHER
(GROUND FLOOR) FLEX CORD FROM ESPRESSO MACHINE IN WALL 400.8
RSLV 03/05/2018 03/05/2018 04/04/2018