Electrical Application Details for App #: M402665
Premises: 220 WEST 16 STREET MANHATTAN BIN: 1013780     Block: 765   Lot: 55
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 220 W 16 ST Census Tract:   81 Health Area:  5600
GROUND Admin Area:   M - MANHATTAN Inspection Area:   R
NEW YORK, NY 10011 Community Board:   104
DOB Cross Street(s):    7 AVENUE,    8 AVENUE
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  10/12/2017 9:02 AM
Application Entered:   10/12/2017 Job Start Date:   10/12/2017
Last Change:   08/22/2025 Job End Date:   11/11/2017
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   BERGMAN EDUARD       On     01/14/2020      
Field Disp:   V - OBJCTN ISSD: JOB INCOMPLT
Energize Recommendation:  
Objection Disposition:  Y - PARTLY REMOVED

License #: 012415 Licensee Name: PETER M PANTELIC
Firm: 004332 Firm Name: PK ELECTRIC INC
Firm Phone: 646-599-2758  Firm Address: 532 EAST NEW YORK AVENUE BROOKLYN NY 11225 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
9 - OTHER
Total Fee:  $100.00
Other Work:   REPLACE END LINE BOX
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: LAURIE BRANT
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  1  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  1  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 01/14/2020
Power Issued: Response:  

Follow-Up:
Contractor's Comments:  REPLACE CON EDISON END LINE BOX

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M402665
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 09/26/2019 09/27/2019 DWB V (27) (4)
INSPECTION COMMENTS: OBJECTION REQUIRE PAA, OBJECTION ISSUED.
 
(2) 01/14/2020 01/14/2020 EDB V Y (55) (2)
INSPECTION COMMENTS: CONTRACTOR NEED TO UPDATE APPLICATION. SEE ATTACHMENT.

OBJECTION FOR APPLICATION #: M402665
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (126) BASEMENT WATER MAIN GROUND NOT INSTALLED ON WATER MAIN
(BASEMENT) 250. WATER MAIN / WATER BONDING JUMPER NOT PROPERLY BOND.
RSLV 09/26/2019 09/26/2019 01/14/2020
 
002 ( 33) KNOCKOUTS ARE NOT CLOSED IN OUTLET BOX
(BASEMENT) 110.12(A), KO SEAL NOT INSTALLED AT DIS SW.
RSLV 09/26/2019 09/26/2019 01/14/2020
 
003 (999) OTHER
(BASEMENT)110.2(A), 200 AMP DIS SW INTERNAL DOOR LOCK BROKEN, IN ACCESSIBLEFOR INSPECTION. BROKEN DURING INSPECTION
OPEN 09/26/2019 09/26/2019
 
004 (999) OTHER
(BASEMENT) PAA REQUIRED FOR MISSING 2ND SET OF FEEDERS
OPEN 09/26/2019 09/26/2019
 
005 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
(CELLAR) 250.24 100 A S. SW. NEUTRAL NOT BONDED
OPEN 01/14/2020 01/14/2020
 
006 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
(CELLAR) 250.50,52 GND ROD ONLY FOR 200 A S. SW.
OPEN 01/14/2020 01/14/2020