Electrical Application Details for App #: M402621
Premises: 1493 BROADWAY MANHATTAN BIN: 1024706     Block: 1015   Lot: 29
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 1501 BROADWAY Census Tract:   119
SUB CELLAR Admin Area:   M - MANHATTAN Inspection Area:   P
NEW YORK, NY 10036 Community Board:   105
Special Place Name:   PARAMONT LEASEHOLD PL
DOB Cross Street(s):   WEST 43 STREET,    WEST 44 STREET
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   10/11/2017 Job Start Date:   10/04/2017
Last Change:   08/22/2025 Job End Date:   10/10/2017
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   BERGMAN EDUARD       On     12/18/2017      
Field Disp:   V - OBJCTN ISSD: JOB INCOMPLT
Energize Recommendation:  
Objection Disposition:  Y - PARTLY REMOVED

License #: 010626 Licensee Name: NEIL KORMAN
Firm: 000042 Firm Name: A.S.M. ELEC AND MACH CORP
Firm Phone: 212-695-0498  Firm Address: 333 WEST 39TH STREET ROOM 201 NEW YORK NY 10018 

Work Started or Filed by Others: YES
Work Category:   R - REHABILITATION Work To Be Done:  
9 - OTHER
Total Fee:  $423.75
Other Work:   OBJECTION REMOVAL
Violations To Be Removed That Were Issued To Or Filed By Another Licensed Firm:     M351816         
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   REQUIRED
Advisory Board Categories:      K - 1000 KVA SERVICE                            
Advisory Board Approval #:   54232     Submittal #: 16A0782  
Owner / Occup:
Owner Business Name: PARAMONT LEASEHOLD PC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  1  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  3  3 PHASE AND N 480VOLT
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
SC1              105         
Buildings Total              105           
Total Units : 105 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 12/18/2017
Power Issued: Response:  

Follow-Up:
Contractor's Comments:  TAKING OVER FOR ANOTHER CONTRACTOR APPLICATION M351816SUBMITTED TO ADVISORY BOARD APPROVED #54232

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M402621
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 10/30/2017 10/31/2017 TUR V (60) (5)
INSPECTION COMMENTS: OBJECTIONS ISSUED , APP ADJUSTED
 
(2) 12/18/2017 12/18/2017 EDB V Y (60) (2)
INSPECTION COMMENTS: SEE ATTACHMENT.

OBJECTION FOR APPLICATION #: M402621
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(CELLAR)110.2(B) ON ADVISORY THE FER RIGHT END OF ROOM SHOWS LEGAL EXIT ITIS NOT AN EXIT IT IS STORAGE AND MAIN WATER PIPES OBSTRUCT EXIT ALLSTORAGE FROM RESTAURANT NOT AS LISTED ON DRAWING
RSLV 10/30/2017 10/30/2017 12/18/2017
 
002 (233) WATER CAN ENTER SERVICE EQUIPMENT
(CELLAR)230.54 WATER IS COKING IN TO END LINE AND DETERIORATING THE COPPERDETAILS NEEDS TO BE WATER TIGHT AND NEEDS MAINTENANCES
OPEN 10/30/2017 10/30/2017
 
003 (276) SECOND ELECTRODE NOT PROVIDED
(CELLAR)250.56 NO SUPPLEMENTAL GROUND FOR SERVICE SWITCH AND BOND STRAP ISNOT AAS PER DRAWING (NOTE CONDUIT FOR WATER GROUND NEEDS STRAPS TOKINDORF
RSLV 10/30/2017 10/30/2017 12/18/2017
 
004 (277) BONDING JUMPER IS NOT PER ART 250.66
(CELLAR)250.66 THE FIRST POIT OF THE SERVICE CONDUIT IN THE END LINE NOTBONDED TO ENCLOSURE CON ED SIDE MIGB NOT BONDED TO ENCLOSURE
RSLV 10/30/2017 10/30/2017 12/18/2017
 
005 (325) ELECTRICAL CLOSETS SHALL NOT BE USED FOR OTHER PURPOSES
(CELLAR)110.25 AMEND ENTIRE 480 VOLT ELECTRICAL ROOM HAS EXCESSIVE STORAGE(ABSOLUTELY NE STORAGE ALLOWED IN ELECTRICAL ROOM BOTH SIDES OF THEWALL
RSLV 10/30/2017 10/30/2017 12/18/2017
 
006 (124) TAP CONDUCTORS ARE NOT WITHIN 10 FT OR WITHIN 25 FT AS PER CODE
(CELLAR)UNDERSIZE TAP CONDUCTORS FOR JOCKEY PUMP 240.21
OPEN 12/18/2017 12/18/2017
 
007 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(CELLAR) EL. RM. NOT PER DRAWING AM. 110.2
OPEN 12/18/2017 12/18/2017