| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
1 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
3 |
3 PHASE AND N 480VOLT |
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (CELLAR)110.2(B) ON ADVISORY THE FER RIGHT END OF ROOM SHOWS LEGAL EXIT ITIS NOT AN EXIT IT IS STORAGE AND MAIN WATER PIPES OBSTRUCT EXIT ALLSTORAGE FROM RESTAURANT NOT AS LISTED ON DRAWING |
RSLV |
10/30/2017 |
10/30/2017 |
12/18/2017 |
| |
| 002 |
(233) |
WATER CAN ENTER SERVICE EQUIPMENT (CELLAR)230.54 WATER IS COKING IN TO END LINE AND DETERIORATING THE COPPERDETAILS NEEDS TO BE WATER TIGHT AND NEEDS MAINTENANCES |
OPEN |
10/30/2017 |
10/30/2017 |
|
| |
| 003 |
(276) |
SECOND ELECTRODE NOT PROVIDED (CELLAR)250.56 NO SUPPLEMENTAL GROUND FOR SERVICE SWITCH AND BOND STRAP ISNOT AAS PER DRAWING (NOTE CONDUIT FOR WATER GROUND NEEDS STRAPS TOKINDORF |
RSLV |
10/30/2017 |
10/30/2017 |
12/18/2017 |
| |
| 004 |
(277) |
BONDING JUMPER IS NOT PER ART 250.66 (CELLAR)250.66 THE FIRST POIT OF THE SERVICE CONDUIT IN THE END LINE NOTBONDED TO ENCLOSURE CON ED SIDE MIGB NOT BONDED TO ENCLOSURE |
RSLV |
10/30/2017 |
10/30/2017 |
12/18/2017 |
| |
| 005 |
(325) |
ELECTRICAL CLOSETS SHALL NOT BE USED FOR OTHER PURPOSES (CELLAR)110.25 AMEND ENTIRE 480 VOLT ELECTRICAL ROOM HAS EXCESSIVE STORAGE(ABSOLUTELY NE STORAGE ALLOWED IN ELECTRICAL ROOM BOTH SIDES OF THEWALL |
RSLV |
10/30/2017 |
10/30/2017 |
12/18/2017 |
| |
| 006 |
(124) |
TAP CONDUCTORS ARE NOT WITHIN 10 FT OR WITHIN 25 FT AS PER CODE (CELLAR)UNDERSIZE TAP CONDUCTORS FOR JOCKEY PUMP 240.21 |
OPEN |
12/18/2017 |
12/18/2017 |
|
| |
| 007 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (CELLAR) EL. RM. NOT PER DRAWING AM. 110.2 |
OPEN |
12/18/2017 |
12/18/2017 |
|